Download the rslogix program and run, Bind lonworks variables, Interpret the network variable data – ProSoft Technology PS56-LON-001 User Manual
Page 9

SlotServer Supplement – LonWorks Open Profile
Page 9 of 16
ProSoft Technology, Inc. is the exclusive provider of FieldServer SlotServers.
For Technical Support call +1 661.716.5100
4.3
Download the RSLogix Program and Run
Use the Who Active or Communications Path directly to Download and Run the Program on the Controller / CPU.
4.4
Bind LonWorks Variables
The SlotServer’s LonWorks Network Variables must be bound to other devices using a Network Management Tool
e.g. LonMaker. See Appendix B for more details on the use of a Network Management Tool to make the bindings.
4.5
Interpret the Network Variable Data
LonWorks Input Variable Values can be found in the Lon_In_01 Tag.
Offset
Network Variable
Name
SNVT_Type
0
nviAmp1
SNVT_amp
1
nviAmp2
SNVT_amp
2 - 4
nviChlr1
SNVT_chlr_status
5
nviCount1
SNVT_count_f
6
nviCount2
SNVT_count_f
7
nviCtInc1
SNVT_count_inc_f
8
nviCtInc2
SNVT_count_inc_f
9
nviFlow1
SNVT_flow_f
10
nviFreq1
SNVT_freq_hz
11
nviHVMod1
SNVT_hvac_mode
12 - 18
nviHVSts1
SNVT_hvac_status
19
nviLev1
SNVT_lev_cont
20 - 21
nviObj1
SNVT_obj_status
22
nviOcc1
SNVT_occupancy
23
nviOcc2
SNVT_occupancy
24
nviPerc1
SNVT_lev_percent
25
nviPerc2
SNVT_lev_percent
26
nviPerc3
SNVT_lev_percent
27
nviPerc4
SNVT_lev_percent
28
nviPerc5
SNVT_lev_percent
29
nviPerc6
SNVT_lev_percent
30
nviPerc7
SNVT_lev_percent
31
nviPerc8
SNVT_lev_percent
32
nviPPM1
SNVT_ppm
33
nviPress1
SNVT_press
34
nviPress2
SNVT_press
Offset
Network Variable
Name
SNVT_Type
35 - 40
nviSetpt1
SNVT_temp_setpt
41
nviState1
SNVT_state
42
nviState2
SNVT_state
43
nviState3
SNVT_state
44
nviState4
SNVT_state
45 - 46
nviSw1
SNVT_switch
47 - 48
nviSw2
SNVT_switch
49 - 50
nviSw3
SNVT_switch
51 - 52
nviSw4
SNVT_switch
53 - 54
nviSw5
SNVT_switch
55 - 56
nviSw6
SNVT_switch
57 - 58
nviSw7
SNVT_switch
59 - 60
nviSw8
SNVT_switch
61
nviTemp1
SNVT_temp_p
62
nviTemp2
SNVT_temp_p
63
nviTemp3
SNVT_temp_p
64
nviTemp4
SNVT_temp_p
65
nviTemp5
SNVT_temp_p
66
nviTemp6
SNVT_temp_p
67
nviTemp7
SNVT_temp_p
68
nviTemp8
SNVT_temp_p
69 - 71
nviTodEv1
SNVT_tod_event
72
nviVltAC1
SNVT_volt_ac
73
nviVltAC2
SNVT_volt_ac
74
nviVolt1
SNVT_volt
75
nviVolt2
SNVT_volt
Table 1: Lon_In_01 Tag Layout.