Appendix b. vendor information – ProSoft Technology PS56-LON-001 User Manual
Page 14

SlotServer Supplement – LonWorks Open Profile
Page 14 of 16
ProSoft Technology, Inc. is the exclusive provider of FieldServer SlotServers.
For Technical Support call +1 661.716.5100
Appendix B. Vendor Information
Appendix B.1. Using LonMaker to Commission a SlotServer
Ensure that the SlotServer and the LonMaker PC are on the same LonWorks network.
Open the existing Network in LonMaker, or create a new Network
Click on “Create New Network” and follow the network wizard, making the following selections:
Network Interface
Network Attached
Management Mode
Onnet (unless you are working offline)
Register Plug-ins required None
Once Visio is open with the Network showing, drag a new device onto the drawing from the toolbox.
Follow the Device prompts, making the following selections
Enter Device Name
Commission device
Specify Device Template
Upload from device
Specify Device Channel
Auto Detect
Specify Device Properties Leave as is (Ping is optional)
Identify Device
Service pin
Device Application Image Leave unchecked
Initial State
Online
Press the service pin on the SlotServer when asked to do so, and the SlotServer will be commissioned.
Drag a new function block onto the drawing from the toolbox. Give the function block a name and ensure
that it is allocated to the SlotServer device.
Once the function block is on the drawing, drag input and output variables onto the function block.
LonMaker will show the variables available for binding. Click on the required variables (or use the select
all option), and they will be commissioned onto the function block.
Connect these variables to other devices by dragging connections from the toolbox and connecting the
variables.
Additional LonWorks information for other Network Managers can be found in the FieldServer LonWorks