14. APPENDIX 1 – RECORDABLE PARAMETERS: SYMBOLS

Negative Q (reactive power) indicates capacitive phase shift. Negative P (real or active power) indi-

cates generation not load and the CTs should be reversed, rotated 180º.

46

DM-4 Power Quality Recorder

Symbol

Description

V1, V2, V3

RMS value of the voltage of phase 1, phase 2, phase 3 respectively

V12, V23 V31

Value of phase to phase voltages

I1, I2, I3

RMS value of the current of phase 1, phase 2, phase 3 respectively

IN

RMS value of the current of the neutral

DC

Continuous component of voltage or current

h01 ∏ h51

Harmonic 01 ∏ Harmonic 51 of voltage or current

ThdV

Factor of total harmonic distortion of the voltage (see paragraph 14.2)

ThdI

Factor of total harmonic distortion of the current (see paragraph 14.2)

Pt, P1, P2, P3

Values of the total active power, of phase 1, phase 2, phase 3 respectively

P12, P32, P13

(only for 3 wires measurement) Value of the power measured by the

Wattmeter. 1-2 and 3-2 respectively (see paragraph 14.3.2)

Qt, Q1, Q2, Q3

Values of the total reactive power, of phase 1, phase 2, phase 3 respectively

Q12, Q32, Q13

(only for 3 wires measurement) Value of the power measured by the

VARmeter 1-2 and 3-2 respectively (see paragraph 14.3.2)

St, S1, S2, S3

Values of the total apparent power, of phase 1, phase 2, phase 3 respectively

S12, S32, S13

(only for 3 wires measurement) Value of the power measured by the

VAmeter 1-2 and 3-2 respectively (see paragraph 14.3.2)

Pft, pf1, pf2, pf3

Value of the total power factors, power factors of phase 1, phase 2, phase 3

respectively

dPft, dpf1, dpf2, dpf3 Values of the total cosΘ, of phase 1, phase 2, phase 3 respectively
Eat, Ea1, Ea2, Ea3 Values of the total active energy, of phase 1, phase 2, phase 3 respectively
Ert, Er1, Er2, Er3

Values of the total inductive reactive Energy, of phase 1, phase 2, phase 3

respectively

-Ert, -Er1, -Er2, -Er3 Values of the total capacitive reactive Energy, of phase 1, phase 2, phase

3 respectively

Est, Es1, Es2, Es3 Values of the total Apparent Energy, of phase 1, phase 2, phase 3 respectively