XIII. APPENDIX D: SEQUENCE OF OPERATIONS

A. SEQUENCE OF OPERATIONS FOR THE HEATING SYSTEM

Mode of Operation

Start

Start trial for

ignition

Standby

(At any time the oil

valve is not energized)

On power interruption, system

shuts off, restarts when

power is restored.

Ignition electrodes spark.

Burner motor energized.

Thermostat calls for heat,

contacts close

Control System Action

Oil valve energized after

15 second time delay.

Flame must be detected

after 45 seconds.

OPA 1 of 2

The retry sequence provides a

60 second wait before ignition

is attempted again.

If flame is not detected, the

oil valve is de-energized,

the ignitor is turned off and

the ignition control module

goes into the "retry" sequence.

Continous safe operation check. If

flame simulation condition present,

system shuts off oil valve,ignitor,

and burner motor; activates fast

flashing LED.