All installations and services must be performed by qualified service personnel.

14

POSITION THEM PER

BURNER MANUFACTURERS

INSTRUCTIONS

REPLACE IGNITION

TRANSFORMER

ARE THE ELECTRODES

ARCING?

IS THE OIL PUMP

OPERATING?

IS THE NOZZLE AND

CAD CELL POSITIONED

PROPERLY? *

IS IGNITION TRANSFORMER
CAPABLE OF PRODUCING A

3/4" ARC? (10,000 VAC)

IS THE COUPLING BETWEEN

THE BURNER MOTOR AND

THE PUMP STRIPPED?

REPLACE COUPLER

IS IGNITION ESTABLISHED?

FURNACE OPERATES FOR

COMPLETE CYCLE?

BURNER RUN NORMAL

CYCLE?

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

No

No

Yes

No

CHECK-BLOWER SPEED

AND RETURN AIR TEMPERATURE

REPLACE PUMP

No

MEASURE MILLIAMPS BETWEEN 'W' &'R'

ON THE T'STAT SUBBASE AND SET HEAT

ANTICIPATOR ACCORDINGLY

No

CHECK FAN ON & OFF SETTINGS

ON FAN & LIMIT CONTROL

ARE THE ELECTRODES ALIGNED

CONTACT SPRINGS TOUCHING

ELECTRODE RODS, & PORCELAIN

CLEAN AND UNCRACKED?

IF PROBLEM PERSISTS CONTINUE TO NEXT SECTION.

* ALSO PERFORM CAD CELL CHECK OUT PROCEDURE(REFER TO INDEX).

IS HEAT ANTICAPATOR SET

TO MILLIAMP SETTING

MEASURED ON SUBBASE?

BLOWER RUNS

NORMAL CYCLE?

IS AIR TEMPERATURE RISE

APPROX. 70 DEGREES F?

PERFORM CAD CELL CHECK

OUT ON PAGE 17.