Thermostat, Psc air handler single stage heat pump – Thermo Pride Premiere XT 16 SEER User Manual
Page 12

12
FIGURE 13: Thermostat Wiring – Single Stage Heat Pump (with YGVI control) – PSC Air Handler
Single Stage Heat Pump (with YGVI control) – PSC Air Handler
ID MODELS
AHP
AHX
THERMOSTAT
S1-THSU21P1b
PSC
AIR HANDLER
SINGLE STAGE
HEAT PUMP
MA
MX
PSC
AIR HANDLER
CONTROL
YORKGUARD VI
CONTROL
C
24 - Volt Common
Y1
First Stage
Compressor
R
24 - Volt Hot
G
Fan
W2
Second Stage Heat
W1/O/B
First Stage Heat
COM
24 - Volt Common
Y/Y2
Second or Full
Stage Compressor
R
24 - Volt Hot
G
Fan
W1
First Stage Heat
W2
Second Stage Heat
Y1
First
Stage Compressor
O
Reversing Valve
Energized in Cool
X/L
Malfunction Light
Y2
Second Stage
Compressor
X/L
Malfunction Light
O
Reversing Valve
Energized in Cool
W1 OUT
First Stage Heat
Y2 OUT
Second Stage
Compressor
R
24 - Volt Hot
C
24 - Volt Common
24VAC Humidifier
(Optional)
24VAC
Electrontic Air Cleaner
(Optional)
Jumper 1 must be set
to “HEAT PUMP”
Jumper 2 must be set
to “O”
Jumper 3 must be set
to “ELEC”
Move the HUM STAT
jumper to “YES”
if humidistat is to be
used.
Refer to AH
documentation
for W1 and W2 electric
heat staging options.
Change FFuel jumper
on the heat pump control
to “OFF”
Part Number:
SAP = Legacy
159480 = 031-09156
Part Numbers:
SAP
524851
500644
Part Number:
S1-2HU16700124
1
2
2
3
1
HUM
Humidity Switch
Open on Humidity Rise
HUM OUT
(24 VAC out)
Humidifier
EAC
(24 VAC out)
Electronic Air Cleaner
External Humidistat
(Optional)
Open on Humidity Rise
3
BS
Bonnet Sensor
BSG
Bonnet Sensor
W
Auxiliary Heat
Y1
Single Stage
Compressor
W2 OUT
Second Stage Heat