Thermo Pride Air Handler Modular MV User Manual
Page 13

13
* May be 0 (no breaker) or 1 (with breaker).
2. Heaters are 3 Phase.
TABLE 11: Electrical Data - (For Single Source Power Supply) - Copper Wire 1 Ø - 208/230-1-60
Models
MV
Heater
Models*
Heater
Amps
240V
Field Wiring
Min. Circuit Ampacity
Max. O.C.P.
Amps/Type
1
75°C Wire Size - AWG
208V
230V
208V
230V
208V
230V
12B
4HK*6500506
20.0
27.54
30.38
30
35
10
8
4HK*6500806
31.3
39.73
44.50
40
45
8
8
4HK*6501006
40.0
49.21
55.38
50
60
8
6
4HK16501306
54.2
64.00
72.80
70
80
4
2
4HK165N1506
60.0
70.88
80.38
90
90
4
3
12D
4HK*6500506
20.0
27.54
30.38
30
35
10
8
4HK*6500806
31.3
39.73
44.50
40
45
8
8
4HK*6501006
40.0
49.21
55.38
50
60
8
6
4HK16501306
54.2
64.00
72.80
70
80
4
2
4HK16501506
60.0
70.88
80.38
90
90
4
3
4HK16501806
73.3
85.32
97.00
90
100
4
3
4HK16502006
80.0
92.54
105.38
100
125
3
1
16C
4HK*6500506
20.0
29.29
31.88
30
35
10
8
4HK*6500806
31.3
41.48
46.00
45
50
8
8
4HK*6501006
40.0
50.96
56.88
60
60
6
6
4HK16501306
54.2
66.40
75.20
70
80
4
2
4HK16501506
60.0
72.63
81.88
90
90
3
3
4HK16501806
73.3
87.07
98.50
90
100
3
2
4HK16502006
80.0
94.29
106.88
100
125
3
1
20D
4HK*6500506
20.0
29.29
31.88
30
35
10
8
4HK*6500806
31.3
41.48
46.00
45
50
8
8
4HK*6501006
40.0
53.08
58.75
60
60
6
6
4HK16501306
54.2
68.40
77.20
70
80
4
2
4HK16501506
60.0
74.75
83.75
90
90
3
3
4HK16501806
73.3
89.19
100.38
90
110
3
2
4HK16502006
80.0
96.42
108.75
100
125
3
1
4HK16502506
100.0
118.08
133.75
125
150
1
1/0
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
TABLE 12: Electrical Data - (For Single Source Power Supply) - Copper Wire - 208/230-3-60
Models
Heat Kit -
Three Phase
Heater
Amps
240V
Field Wiring
Min. Circuit Ampacity
Max. O.C.P.
1
Amps/Type
75°C Wire Size - AWG
208V
230V
208V
230V
208V
230V
12B
4HK06501025
23.1
30.9
34.3
35
35
8
8
12D
4HK06501025
23.1
30.9
34.3
35
35
8
8
4HK06501525
34.7
43.4
48.8
45
50
8
8
4HK06501825
41.4
50.6
57.1
50
60
8
6
16C
4HK06501025
23.1
32.6
35.1
35
35
8
8
4HK06501525
34.7
45.1
49.6
45
50
8
8
4HK06501825
41.4
52.4
58.0
60
60
6
6
20D
4HK06501025
23.1
34.8
37.6
35
40
8
8
4HK06501525
34.7
47.3
52.1
50
60
8
6
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.