Soft-start characteristics, Soft-stop characteristics, Rvs-ax ratings and frame sizes – SAF OPAL LT User Manual
Page 4: Starter selection

Starter Selection
3
The RVS-AX electronic soft starter incorporates six
thyristors to start a three-phase squirrel cage induction
motor. By supplying a slowly increasing voltage, it
provides soft start and smooth stepless acceleration,
while drawing the minimum current necessary to start
the motor.
A Soft Stop feature can be enabled when the Ramp-
Down potentiometer is adjusted. When used, upon stop
signal (open contact terminals 1 and 2), motor's voltage
is slowly reduced to zero.
Soft-Start Characteristics
M%
Torque
I%
U%
Current
Voltage
100
100
400
10
50
100
Soft-Stop Characteristics
The Soft-Stop characteristic
may be used for controlled
deceleration of pumps and high
friction loads.
RVS-AX ratings and Frame sizes
Max. Motor
FLA (Amp)
Starter Type
FLC (Amp.)
Frame Size
(A
luminum
)
8
RVS-AX 8
17
RVS-AX 17
31
RVS-AX 31
44
RVS-AX 44
A1
58
RVS-AX 58
72
RVS-AX 72
A2
85
RVS-AX 85
105 RVS-AX
105
A3
145 RVS-AX
145
170 RVS-AX
170
A4
Dimensions (mm) & Weights (Kg)
Size
Width
Height
Depth
Weights (Kg)
A1 120 232 105
2.6
A2 129 275 185
5
A3 129 380 185
8.4
A4 172 380 195
11.8
The starter should be selected in accordance with the
following criteria:
1. Motor Current & Starting Conditions
Select the starter according to motor's Full Load
Ampere (FLA) - as indicated on its nameplate (even if
the motor will not be fully loaded).
The RVS-AX is designed to operate under the
following maximum conditions:
Ambient
Temp.
I start
Acc. Time
300% In
30 Sec
350% In
20 Sec
40° C
400% In
5 Sec
Max.
Starts
per
Hour: four (4) starts per hour at
maximum ratings and up to 10
starts per hour at light load
applications (consult factory).
Note
: For very frequent starts (inching applications)
the inching current should be considered as the
Full Load Current (FLC) – consult factory.
2. Mains Voltage
U%
Voltage
10
50
100
Each starter is factory set for one of the following
levels according to the Ordering Information.
Voltage
Tolerance
380 - 415 V
+10 -15 %
440 V
+10 -15 %
460 - 500 V *
+10 -15 %
575 - 600 V
+10 -15 %
Frequency: 50 / 60 Hz.
* Starter’s rated 460-500VAC can be field modified
for system voltage of 220-240V, by placing the
internal Jumper J3 as shown below.
W
V
U
1 2 3
J3
1
2
3
1
2
3
220 to 240V
460 to 500V