SAF OP-STOP DCI User Manual
Page 9

OP-STOP DC INJECTION BRAKE
Page 4
2 SPECIFICATIONS
2.1 POWER RATING
POWER
200-600VAC, 50/60 Hz
CONTROL
115 VAC, 50 Hz or 120 VAC, 60 Hz
RATING
Intermittent duty, See Section 2.2
300% for 30 seconds, once every 30 minutes
All models have 1600V PIV SCR's
CONTACTS
DC injection relay contacts rated at 1A, 120VAC
PROTECTION Short circuit by HRC fuses or circuit breaker
(supplied upon request)
Voltage surge protection by snubber's and MOV's across the SCR's
2.2 CURRENT AND FUSE RATING
CURRENT RATING
DCI
MODEL
AMPS MOTOR
HP @ 575 V
MOTOR
HP @ 460V
FUSE
AMPS
SCR
TYPE
DCI-20
20.0
20.0
15.0
20.0
Module
DCI-40
40.0
40.0
30.0
40.0
Module
DCI-80
80.0
75.0
60.0
80.0
Module
DCI-125
125.0
125.0
100.0
125.0
Module
DCI-200
200.0
200.0
150.0
200.0
Disc
DCI-300
300.0
300.0
250.0
300.0
Disc
DCI-500
500.0
500.0
400.0
500.0
Disc
2.2.1 NOTES
2.2.1.1 The HP listing is for reference only. For proper selection use the current rating.
2.2.1.2 The fuses recommended are Class J time-delay type. This fuse is being suggested even
though it may not protect the SCR in an output shorted condition while braking. It will
protect the unit when starting to operate into a shorted output. In the case of a shorted
SCR, the fuse is there to clear the fault only.
2.2.1.3 The RMS AC line current is equal to : AC RMS = DC Amps x
√ Duty Cycle Assuming
10A motor, OP-STOP set at 300% current (30 A DC), free wheeling for 70% of the
cycle, then the AC current is 16A.
2.2.1.4 All OP-STOP models are built without cooling fans because they are short duty rated.