SAF OP-STOP DCI User Manual
Page 19

OP-STOP DC INJECTION BRAKE
Page 14
MODEL
MOTOR
AMPS
BURDEN
RESISTOR (¼ W)
EFFECTIVE CT
RATIO
SS6-15 with DCI
10.0
68
Ω
750 : 1
15.0
47
Ω
DCI-20
or
SS6-30 with DCI
20.0
39
Ω
750 : 1
30.0
27
Ω
DCI-40 or
SS6-50 with DCI
40.0
39
Ω
1500 : 1
50.0
33
Ω
DCI-80 or
SS6-80 with DCI
60.0
39
Ω
2500 : 1
80.0
33
Ω
DCI-125 or
SS6-125 with DCI
100.0
27
Ω
2500 : 1
125.0
22
Ω
DCI-200 or
SS6-200 with DCI
150.0
18
Ω
2500 : 1
200.0
12
Ω
DCI-300 or
SS6-360 with DCI
200.0
27Ω
5000 : 1
300.0
18
Ω
DCI-500 or
SS6-500 with DCI
400.0
22
Ω
8500 : 1
500.0
18
Ω
4.5.2 WITH POWER ON
4.5.2.1 Run the motor up to full speed and command the starter off. If the motor reaches zero
speed from the DC injection cycle, close the switch to the Disable Input to disable the
braking.
4.5.2.2 Re-adjust the braking torque pot, RV2, if the actual braking time has to be increased or
decreased to bring the motor to zero speed.
4.5.2.3 Once the braking torque is set, then adjust RV1 to match the DC injection time with the
actual stopping time of the motor. Typically, the injection should decease when the motor
is at zero speed or shortly after. LD1, DC INJCT is an indication of braking. Each 10%
graduation in RV1 corresponds to approximately 6 seconds.
WARNING!
ALLOW TIME FOR THE MOTOR TO COOL BEFORE ANOTHER
START / STOP SEQUENCE IS INITIATED
FREQUENT START / STOP COULD CAUSE MOTOR DAMAGE
DUE TO OVERHEATING