MS6 REDUCED VOLTAGE STARTER

Page 10

2 SPECIFICATIONS

2.1 POWER RATING

Power

3 phase, 200-600 VAC, 50/60Hz

Control

115VAC 50Hz or 120VAC 60Hz

Rating

See Section 2.2

All models have 1600V PIV SCR’s

Digital Inputs 120VAC,

2mA

Digital Outputs Relay contacts rated at 0.2A, 120VAC
By-Pass Output Relay contact rated at 5A, 120VAC
Analog Input

0 – 10Vdc

Analog Output 0 – 5Vdc, 5mA max
Protection

Short circuit by HRC fuses or circuit breaker (supplied upon request)

2.2 MAXIMUM RATINGS

HORSE POWER

OPAL PRO

MODEL

230VAC

460VAC

575VAC

MS6-30 10 25 30
MS6-50 20 40 50
MS6-80 30 60 75

MS6-125 40 100

125

MS6-250 100 200 250
MS6-420 175 350 420
MS6-500 200 400 500
MS6-600 200 500 600
MS6-800 300 600 800

* HP Rating for estimate only. Size by motor FLA

2.3 SERVICE CONDITIONS

Elevation

For altitudes in excess of 1000 meters (3300 feet) above sea level, all
assemblies must be de-rated 1% for every 100 meters (330 feet) above

Ambient Temperature Do not install in areas where the ambient temperature falls below
0

°C(32°F) or exceeds 40°C(104°F)