MS6 REDUCED VOLTAGE STARTER
Page 10
2 SPECIFICATIONS
2.1 POWER RATING
Power
3 phase, 200-600 VAC, 50/60Hz
Control
115VAC 50Hz or 120VAC 60Hz
Rating
See Section 2.2
All models have 1600V PIV SCR’s
Digital Inputs 120VAC,
2mA
Digital Outputs Relay contacts rated at 0.2A, 120VAC
By-Pass Output Relay contact rated at 5A, 120VAC
Analog Input
0 – 10Vdc
Analog Output 0 – 5Vdc, 5mA max
Protection
Short circuit by HRC fuses or circuit breaker (supplied upon request)
2.2 MAXIMUM RATINGS
HORSE POWER
OPAL PRO
MODEL
230VAC
460VAC
575VAC
MS6-30 10 25 30
MS6-50 20 40 50
MS6-80 30 60 75
MS6-125 40 100
125
MS6-250 100 200 250
MS6-420 175 350 420
MS6-500 200 400 500
MS6-600 200 500 600
MS6-800 300 600 800
* HP Rating for estimate only. Size by motor FLA
2.3 SERVICE CONDITIONS
Elevation
For altitudes in excess of 1000 meters (3300 feet) above sea level, all
assemblies must be de-rated 1% for every 100 meters (330 feet) above
Ambient Temperature Do not install in areas where the ambient temperature falls below
0
°C(32°F) or exceeds 40°C(104°F)