beautypg.com

Technical data – Riello UPS Sentinel Pro (700 - 3000 VA) User Manual

Page 24

background image

24

TECHNICAL DATA

UPS MODELS

SEP 700

SEP 1000

SEP 1000 ER

SEP 1500

SEP 2200

SEP 2200 ER

SEP 3000

SEP 3000 ER

INPUT

Nominal voltage

[Vac]

220 - 230 - 240

Maximum operating voltage

[Vac]

300

Nominal frequency

[Hz]

50 - 60

Nominal current (1)

[A]

3.3

4.5

6.5

9.5

12.5

BATTERY

Recharge time (standard versions)

[h]

< 4h for 80% of the load

Expandability and nominal
voltage of the Battery Box

Not

expandable

36Vdc

Not

expandable

72Vdc 72Vdc

Charging current
(for ER versions only)

Not

applicable

8A

Not

applicable

8A 8A

OUTPUT
Nominal voltage (4)

[Vac]

Selectable: 220 / 230 / 240

Frequency (2)

[Hz]

Selectable: 50, 60 or auto sensing

Nominal power

[VA]

700VA

1000VA

1500VA

2200VA

3000VA

Nominal power

[W]

560W

800W

1200W

1760W

2400W

Overload: 100% < load < 110%

Bypass line available:

activates the bypass after 2 seconds

locks

after

120

seconds

Bypass line not available:

locks after 60 seconds

Overload: 110% < load < 150%

Bypass line available:

activates the bypass after 2 seconds

locks after 4 seconds

Bypass line not available:

locks after 4 seconds

Overload load > 150%

Bypass line available:

activates the bypass instantly

locks after 1 second

Bypass line not available:

locks after 0.5 seconds

OTHER
Leakage current to earth

[mA]

< 1,5mA

< 2mA

Ambient temperature (3)

[°C]

0 – 40

Humidity

< 90% without condensation

Protection devices

excessively low batteries - overcurrent - short circuit - overvoltage -
undervoltage - circuit breaker

Dimensions W x D x H

[mm]

158 x 422 x 235

190 x 446 x 333

Weight [kg]

11

13

14

26

28

Weight (for ER versions only)

[kg]

Not

applicable

7

Not

applicable

14 15


For more details please consult the web site

(1)

at nominal load, nominal voltage of 230 Vac, battery charging

(2)

If the mains frequency is within ±5% of the selected value, the UPS is synchronised with the mains. If the frequency is
out of the tolerance range or operating from the battery, the frequency is the one selected ±0.1%

(3)

20 - 25 °C for longer battery life

(4)

To keep the output voltage within the indicated range of precision, recalibration may be necessary after a long period
of operation

This manual is related to the following products: