Precision Digital PD570 User Manual

Page 39

background image

To prevent electric shock, be sure to turn off power to the Nova Controller and the source circuit
breaker before wiring.

!

CAUTION

7.11 Communication Wiring (RS-485)

„ Up to 31 slave controllers (Nova series controllers equipped with the RS-485 serial communication

option) can be connected.

„ Be sure to connect terminating resistors (220

Ω, 1/4 W) to slave and master controllers at

communication channel ends as shown above.

Master Station

NOVA Controller

Terminating Resistor

SHIELD

RTX+

RTX+

RTX+

RTX-

RTX-

RTX-

SG

SG

SG

Terminating Resistor

NOVA Controller

PD570 Series Nova Process and Temperature Limit Controller

Instruction Manual