5.4 Retransmission Group (G.RET)
Press SET/ENT key to select retransmission group. (Refer to parameter map.)
This parameter sets the type of retransmission mode to use. The setting options are PV,
SP, and LPS. See notes below for an explanation of the retransmission types.
The default setting is PV.
PV
These parameters are used to scale the retransmitting output. They set the high and low
limits for th e retransmission output scale, as shown below. The retransmitting outputs will
transmit 4 mA at th e low limit (RETL) and 20 mA at the high limit (RETH) values. These
limi ts are used when the retransmission type is set to PV or SP.
PV
PV
PV
?
NOTE
RETL
4.0 mA
12.0 mA
RETH
20.0 mA
PV and SP Type Retransmission Scale
PV type retransmits based on the input value, SP retransmits based on the set point value.
Display
Parameter
Setting Range
Unit
Default
Remark
RET
RETH
RETL
Select Ret Type
PV, SP, LPS
ABS
PV
Ret Scale
High Limit
T/C, RTD: INRH to INRL
mV, V: INSH to INSL
RETH > RETL
AEU
INRH
Ret Scale
Low Limit
AEU
INRL
PWD
Q G.CTL Q G.IN
K R
G.COM
Q G.RET Q G.ALM
ST
ST
ST
ST
ST
T
Retransmission Group Parameter Summary
LPS Type Retransmission
LPS (Loop Power Suppy) retransmitting outputs will transmit a 14-18 VDC @ 20 mA power supply output.
PD570 Series Nova Process and Temperature Limit Controller
Instruction Manual