beautypg.com

MEDC PAS2 User Manual

Page 3

background image

12

© Cooper MEDC 2012

4. maIntenance

During the working life of the unit, little or no maintenance is required. However,

if abnormal or unusual environmental conditions occur due to plant damage or

accident etc., then visual inspection is recommended.

If a fault should occur, it is recommended that the unit be returned to MEDC for

repair. All parts are replaceable.

If you have acquired a significant quantity of units, it is recommended that spares

are also made available. Please discuss your requirements with the Technical

Sales Engineers at MEDC.

5. certIfIcatIon/approVals

Please refer to marking on the unit for specific approval details.

• UL listed for use in

Class I, Zone 1, AExd IIC T5.

USA (USL) and

Class I, Division 2, Groups A, B, C & D.

Canada (CNL)

Class II, Division 2, Groups F & G.

• UL Standards

UL 2279 & UL464.

• ULC Standards

CAN/ULC-S525-07

6. certIfIed temperature

–55°C to +70°C

–67°F to +158°F

11/

© Cooper MEDC 2012

General arranGement

All cable glands should be of an equivalent NEMA/IP rating to that of the unit

and integrated with the unit such that this rating is maintained.

Once termination is complete, carefully push the cover back onto the unit, avoid-

ing damage to the mating surfaces. Tighten the 6 off cover screws evenly, to

ensure maintenance of the required gap between the cover and enclosure.

3. operatIon

The unit is initiated directly from the power source.

For all versions, a 5-way DIL switch selects the tone required from the list shown.

The DB3P includes two 5-way DIL switches to select any two tones from the list.

These units can be switched between any two of the tones listed by either:-

· Reversing the polarity of the power supply, or

· By a 3 wire common +ve system, switching between the two –ve lines.

10

11

/

16

"

271mm

Ø 4

5

/

8

" / 117mm

Ø 6

11

/

16

" / 170mm

FIXING HOLE Ø

1

/

2

" /

FIXING HOLES Ø ALL

11

/

32

" / 9mm (2 POS.)

2 x

1

/

2

" NPT ENTRIES MAX

7

19

/

32

"

193mm

1

3

/

16

"

30mm

1

3

/

16

"

30mm

POSITION 2 IS USED IF ONLY 1 x

1

/

2

" NPT ENTRY REQUIRED

2

3

/

32

"

53mm

ALL DIMENSIONS IN INCHES AND MILLIMETERS

11/12