Carefully replace the cover assembly back onto the base, avoiding damage to the mating surfaces. Replace

the 6 off M8 screws (6.0mm A/F hexagon key) into the holes in the cover assembly and tighten evenly. Ensure

the O-ring is seated correctly on the cover during re-assembly. Ensure the required maximum gap of 0.2mm is

maintained between the cover and the base once assembled.

5.0 CERTIFICATION/APPROVALS

IECEx units

Certified to IEC60079-0 and IEC60079-1

Ex d unit (IEC certification No. IECEx BAS 10.0049)

60W units:

Ex d IIB T4 (-55°C to +55°C) Gb

T5 (-55°C to +30°C) Gb

100W units:

Ex d IIB T3 (-55°C to +20°C) Gb

The IECEx certificate and product label carry the IECEx equipment protection level marking

Gb

Where Gb signifies suitability for use in a Zone 1 surface industries area in the presence of gas.

ATEX units

Certified to EN60079-0 and EN60079-1

Ex d unit (ATEX certification No. BAS99ATEX2196)

60W units:

Ex d IIB T4 (-55°C to +55°C) Gb

T5 (-55°C to +30°C) Gb

100W units:

Ex d IIB T3 (-55°C to +20°C) Gb

The ATEX certificate and product label carry the ATEX group and category marking:
II 2 G
Where:

Signifies compliance with ATEX

II Signifies suitability for use in surface industries

2 Signifies suitability for use in a zone 1 area

G Signifies suitability for use in the presence of gases

02/11