Installation instructions – MCZ Stub User Manual
Page 7

5
2-INSTALLATION INSTRUCTIONS
The requirements stipulated in this chapter refer to the regulations of the Italian installation Standard UNI 10683. In any case, always
comply with the regulations in force in the country of installation.
THE OPERATING ENVIRONMENT
For correct operation and even distribution of heat, the product must be placed where the air required for combustion can flow, in
accordance with the installation regulations and the standards in force in the country of installation.
The volume of the installation environment must not be less than 25 m
3
.
The air must enter through permanent openings in the walls that reach outside with a minimum section of 100 cm
2
in the case of a non-
Oyster installation, i.e. without external ducted combustion air.
These openings must be made in such a way that it is impossible for them to be obstructed in any way.
Air can also be drawn from adjacent rooms to the one that is to be ventilated, provided they have an external air inlet and are not used as a
bedroom or bathroom or where there is a fire hazard, such as: garages, timber storerooms, warehouses of flammable materials, observing
under all circumstances the provisions of all the applicable standards in force.
• If the product is placed too close to the wall it could cause overheating and damage the plaster (yellowing,
cracking, etc.).
• The product must be connected to a flue or a vertical duct that can expel the smoke at the highest point of the
building.
• The product must be connected to a flue or an internal or external vertical duct in compliance with current
regulations.
• The smoke derives from the combustion of wood essence and if it comes in contact with or close to walls, the
latter can become dirty.
• The external air inlet must be drilled before positioning the product (except in the case of installation with
Oyster technology).
• The floor of the room where the product will be installed must be adequately sized to withstand its weight.
POSITIONING
In the case of simultaneous installation with other heating appliances, provide appropriate air inlets for each one (according to the
instructions of each product).
The product cannot be installed in the following places (except for sealed or closed operation appliances with
external ducted combustion air intake):
• in bedrooms or bathrooms;
• in rooms where there are liquid fuel appliances with continuous or intermittent operation that draw the
combustion air from the room they are installed in;
• in rooms where there are B-type gas heating appliances, with or without domestic hot water production and
interconnecting rooms;
• where another heating appliance is installed without an independent air flow.
It is forbidden to place the product in an explosive atmosphere.
Technical Dept. - All rights reserved - Reproduction is prohibited