Trouble check for the cooling cycle, Back to top – Equator RF 800 User Manual
Page 24

23
Sy m p tom
C a use
.The EVAP c ools d ow n a nd w arm s
a gain.
.The c ond enser w arm s in prop ortion
a s the EVA P coo ls.
.The p roc ess rep ea ts ag ain.
M oisture in the refrig erant
ca uses the m a lfunction.
The c om presso r is
d efective.
Too m uch re frig erant.
Refrig e rant leaks.
Sugge stions
4.Trouble check for the cooling cycle
.The c ond enser is co ld.
.The EVAP is not co ld.
.The tem p era ture of the com pre ssor
is high.
.No d ifference in tem pe ratures
betw een suc tion pip e a nd disc ha rg e
pip e.
.The tem pera ture of the com p re ssor
is m ainta ined a t roo m tem p e ra ture.
.The EVA P d oe s not cool do w n.
.Frost on the suction pip e.
.The c ond enser is ove rheated.
.The re frig era tion in the EVAP is
not effecient.
.The cond enser is co ld.
.The com pressor surface tem p era ture
is hig h.
.The re frige ra tion is not ea sily get
c ooled.
Rep lace the re frige ra nt.
Loc ate d the disturb ed section
and m ake rep a irs.
Rep lac e the c om p resso r.
Rep lace the re frige ra nt.
A fter w elding the leake d
spo t, rep lace the refrig e ra nt.
Back to top