DVS205

Technical Specifications

Page

3

Power

Input at 0 to 75°C (32 to
167°F)

8 to 30 Vdc, 10 mW average

Input at –40 to 0°C (–40 to
32°F)

8.5 to 30 Vdc, 10 mW average

Physical

Dimensions

120 mm H by 163 mm W by 89 mm D (4.7 in. H by 6.4 in. W by 3.5 in. D)

Weight

2.2 kg (4.9 lb)

Vibration Effect

Sensor outputs shall not shift more than +0.1% of upper range limit per g from 5 to 2000
Hz in any axis when tested per IEC 770, Section 6.2.14.

Construction

Standard

Transducer is all stainless steel construction with silicone fill fluid,
316L diaphragms and glass-filled PTFE o-rings.

Coupling is A360 Aluminum with urethane coating.

Optional

Transducer includes Hastelloy C-276 wetted parts (construction is
NACE compliant per MR0103 and ISO15156/MR0175), inert fill fluid.

Coupling is available316 stainless steel.

Mounting

Factory-installed on enclosure of FB103, FB107E, and FB503 units. See respective
technical specifications for unit mounting options.

Connections

Process

1/4-18 NPT on 2-1/8 inch centers (on coplanar flange)

Environmental

Same as the FloBoss unit in which it is installed.

Process Seals per ANSI/ISA
12.27.01

Meets requirements for a Single Seal device as defined by ANSI/ISA 12.27.01.
Installation must adhere to the following process temperature limits:

Standard

Silicone Fill
Sensor

–40 to 100°C (–40 to 212°F)

Process
Temperature (at
transmitter
isolator flange)

Inert Fill Sensor

–18 to 85°C (0 to 185°F)

Note: Process temperatures above 85°C (185°F) require you to

lower the product’s maximum ambient temperature rating by
a 1.5:1 ratio. To determine the adjusted maximum
temperature rating, perform the following calculation:

Adjusted max T

amb

= Product Max T

amb

– [(Actual Process

T

amb

– 85°C (185°F)) * 1.5]

Example:
Adjusted Max T

amb

= 75°C – [(95°C – 85°C) * 1.5] = 60°C.

Approvals

Same as the FloBoss unit in which it is installed.