Guide Specifications

7

3.0

G

UIDE

S

PECIFICATIONS

3.1

General

Each condenser shall consist of housing, condenser coil, propeller fans direct-driven by individual fan

motors, fan guards, electrical controls and mounting legs. The air-cooled condenser shall have a

_____volt, 3-phase, _____ Hz power supply.

3.2

Coil

Liebert manufactured coil shall be constructed of copper tubes in a staggered tube pattern. Tubes are

expanded into continuous, corrugated aluminum fins. The fins have full depth fin collars completely

covering the copper tubes, which are connected to heavy wall Type "L" headers. Inlet coil connector

tubes pass through relieved holes in the tube sheet for maximum resistance to piping strain and

vibration. Coils are factory leak-tested at a minimum of 300 psig (2068kPag), dehydrated, then filled

with a nitrogen holding charge and sealed for shipment.

3.3

Fans

Fans shall have aluminum blades secured to corrosion protected steel hubs. Fans shall be secured to

the fan shaft by means of a heavy-duty keyed hub and dual setscrews. Fan diameter shall be 26"

(660mm) or less. Fans shall be factory balanced and run before shipment. Fan guards shall be heavy

gauge, close-meshed steel wire with corrosion resistant PVC finish that shall be rated to pass a

675-hour salt spray test.

3.4

Fan Motors

The variable speed fan motor shall be an inverter duty motor with permanently lubricated ceramic

bearings. The Liebert variable frequency drive control system shall provide overload protection for

the variable speed motor. Each ambient-temperature-controlled fan motor shall have built-in over-

load protection. All motors shall have rain slingers, permanently lubricated bearings and shall be rig-

idly mounted on die-formed galvanized steel supports.

3.5

Head Pressure Control

The Liebert VFD Condenser control system shall include a variable frequency drive, inverter duty fan

motor operating from 0% to 100% motor RPM based on head pressure, refrigerant pressure transduc-

ers, ambient-temperature thermostat(s), motor overload protection and electrical control circuit, fac-

tory-wired in the control panel. VFD control shall be furnished on the fan adjacent to the connection

end of the condenser, which runs continuously with the compressors. Other condenser fans shall be

controlled by ambient thermostats and are either On or Off. This system permits operation at temper-

atures as low as -20°F (-28.9°C).

3.6

Housing

The condenser housing shall be constructed of bright aluminum sheet and divided into individual fan

sections by full width baffles. Structural support members, including coil support frame, motor and

drive support, are galvanized steel for strength and corrosion resistance. Aluminum legs are provided

with rigging holes for hoisting the unit into position.

3.7

TVSS and Unit Disconnect Switch

Transient Voltage Surge Suppression and locking disconnect shall be factory-installed and wired in

the enclosed condenser electrical panel section.

3.8

Alarm Contacts

Normally open, dry contacts shall be provided for indication of VFD and TVSS alarm condition.

3.9

Electrical Controls

All electrical connections and controls shall be provided in a weatherproof enclosure. The enclosure

shall be integral with the condenser for pleasing appearance as well as functional protection.