beautypg.com

Planning, Installation checklist, Chapter 1 – Emerson Process Management MICRO MOTION T-SERIES User Manual

Page 5: 1planning, 1 installation checklist

background image

1

Planning

Topics covered in this chapter:

Installation checklist

Best practices

Environmental limits

Recommendations for hygienic and self-draining applications

1.1

Installation checklist

Make sure that the hazardous area specified on the sensor approval tag is suitable
for the environment in which the sensor is installed.

Verify that the local ambient and process temperatures are within the limits of the
sensor. See

Environmental limits

.

If your sensor has an integral transmitter, no wiring is required between the sensor
and transmitter. Follow the wiring instructions in the transmitter installation manual
for signal and power wiring.

If your transmitter has remote-mounted electronics, follow the instructions in this
manual for wiring between the sensor and the transmitter, and then follow the
instructions in the transmitter installation manual for power and signal wiring.

For the wiring between the sensor and the transmitter, consider maximum cable
lengths (see

Table 1-1

and

Table 1-2

). The maximum distance between the sensor

and transmitter depends on the cable type. For all types of wiring, Micro Motion
recommends using Micro Motion cable.

Maximum lengths for Micro Motion cable

Table 1-1:

Cable type

To transmitter

Maximum length

Micro Motion 9-wire

9739 MVD transmitter

1000 ft (300 m)

All other MVD transmitters

60 ft (20 m)

Micro Motion 4-wire

All 4-wire MVD transmitters

1000 ft (300 m)

Maximum lengths for user-supplied 4-wire cable

Table 1-2:

Wire function

Wire size

Maximum length

Power (VDC)

22 AWG (0,35 mm

2

)

300 ft (90 m)

20 AWG (0,5 mm

2

)

500 ft (150 m)

18 AWG (0,8 mm

2

)

1000 ft (300 m)

Signal (RS-485)

22 AWG (0,35 mm

2

) or larger

1000 ft (300 m)

Planning

Installation Manual

1