Troubleshooting table

Problem

Causes

Solution

The humidifier does
not turn on

1. No electrical power;
2. On/Off switch of the humidifier in Off

position (O);

3. Improper connection;
4. Blown fuses;
5. Transformer fault;
6. Humidistat or air flow switch not closed

1. Check the external fuses and breakers

and for power at the humidifier;

2. Turn the On/Off switch On (I);
3. Check that the power wires are properly

inserted in the terminal block;

4. Check the condition of fuses f1/f2/f3;
5. Check that the voltage across the

secondary winding of the transformer is
24vac

6. Jump out airflow & humidistat

The humidifier does
not start operation

1. Humidistat or air flow switch open;
2. The humidistat has not been connected

correctly;

3. Humidistat fault

1. Fix or replace humidistat or air flow switch;
2. Check the external wiring

The humidifier fills
with water without
producing steam

1. Too much backpressure in steam hose;
2. Cylinder drain screen blocked;
3. Lime scale in the fill cup;
4. Drain valve malfunction

1. Check that the steam outlet pipe is not

bent or choked;

2. Clean the filter;
3. Clean the fill cup;
4. Check for the presence of 24vac at the

drain electrovalve and/or replace drain
electrovalve

Breaker opens

Circuit breaker is under-rated

Check that the thermal-magnetic overload
switch is rated for a current of at least 1.5
times the rated current of the humidifier

The humidifier wets
the duct

1. The distributor is not installed correctly;
2. Humidifier over-sized;
3. Humidifier active when the fan in the

duct is off

1. Check that the steam distributor is

installed correctly;

2. Change humidifier model;
3. Check the connection and condition of the

airflow switch

The humidifier wets
the floor below

1. The humidifier drain is blocked;
2. The supply water or overflow circuit has

leaks;

3. The steam outlet pipe is not properly

fastened to the cylinder

1. Clean the drain in the bottom tank;
2. Check the entire water circuit;
3. Check the fastening of the pipe clamps on

the steam outlet