beautypg.com

Convenient, from selection to maintenance, M c b a, Etl listed to ul standard 1008 for safety – Emerson SmartSwitch User Manual

Page 3: Wall mount rack mount under floor

background image

With separate sections for

power connections and

electronics, Liebert

SmartSwitch can sustain

power to the load even when

the electronics module is

being swapped for service.

Three different configurations allow the unit to be

placed under a raised floor, mounted on a wall or used

in a rack, based on your site needs.

Logic and Power Supplies

Source 1

Source 2

Output

Connections and

Bypass Section

Hot-Swap

Electronics Section

3.76"

COVER
PLATE

STATUS CONTACTS CONNECTOR

RS-232 CONNECTOR

11.1"

10.7"

2.5"

AIR EXHAUST AREA
DO NOT BLOCK

8.0"

8.0"

2.0"

.75"

20.0"

51

51

52

52

ALTERNATE SOURCE

PREFERRED SOURCE

INPUT, OUTPUT
AND CONTROL
CONNECTIONS
LOCATED BEHIND
REMOVABLE
ACCESS DOORS

INPUT

SOURCE 52

SOURCE 51

M C B A

M C B A

M C B A

DO

DO

DO

Bypass Switch
Transfer Control

NORMAL

MAN.
XFER
51

MAN.
XFER
52

BYPASS
TO 51

BYPASS
TO 52

BYPASS / TRANSFER SWITCH

(LOCATED BEHIND KEYLOCK COVER)

25.4"

25.4"

26.9"

LED SWITCH STATUS
INDICATORS AND LABELS

REMOVABLE "HOT-SWAPPABLE"
ELECTRONICS MODULE

KEYLOCK LATCH

0.28" (7MM)
(6 MTG. HOLES)

2.25"

2.25"

3.15"

1/2" KNOCKOUT
0.88" (22mm)
(3 PLACES)

AIR INTAKE
2 SIDES

TOP VIEW

FRONT VIEW

RIGHT SIDE VIEW

BOTTOM VIEW

18.3" (465mm)

19" (483mm)

17.25"

(438mm)

20.4"

(518mm)

NORMAL

MAN.
XFER
51

MAN.
XFER
52

BYPASS
TO 51

BYPASS
TO 52

BYPASS / TRANSFER SWITCH

(LOCATED BEHIND KEYLOCK COVER)

KEYLOCK LATCH

1/2" KNOCKOUT
0.88" (22mm)
(TYP. 8 PLACES)

REMOVABLE

"HOT-SWAPPABLE"

ELECTRONICS

MODULE

18.5"

(469mm)

3.5" (88.9mm)

5.20"

(132mm)

0.85"

(21.5mm)

INPUT & OUTPUT
CONNECTIONS

OUTPUT
RECEPTACLE

STATUS CONTACTS
CONNECTOR

RS-232 CONNECTOR

0.279" (7mm) x
0.406" (10mm) SLOT
(4 SLOTS)

LED SWITCH STATUS
INDICATORS

11"

(279mm)

"HOT-SWAPPABLE"
ELECTRONICS

20"

(508mm)

20"

(508mm)

51

52

51

52

PERFERRED SOURCE

ALTERNATE SOURCE

INPUT CONNECTIONS

OUTPUT RECEPTACLE

RELAY

CONTACTS

& RS-232

PORT

WALL MOUNT

RACK MOUNT

UNDER FLOOR

Convenient, from selection to maintenance.

Choice of output receptacles and connector is

available to match your load specifications, simplifying

system installation and setup.

Selectable preferred input feature allows you to

determine the normal and alternate power source

of your choice without rewiring or load shutdown.

Integral maintenance bypass to both input sources

provides a safe and fast solution to servicing the

Liebert SmartSwitch without disturbing your

protected equipment.

Hot swappable electronics module and bypass

feature allow your protected equipment to remain up

and running, even when the Liebert SmartSwitch

module is being replaced or serviced.

LED indicators provide at-a-glance operating status.

Eight output contacts are available for remote status

indication. RS232 ASCII communications port allows

setpoint control and remote monitoring.

ETL Listed to UL Standard 1008 for safety.

CE Mark (50 Hz) — complies with EMC and low voltage

directives.

3

Liebert SmartSwitch includes
manual transfer test capability
to assure continued proper
operation.

The unit is available
with your choice
of receptacles and
connector,simplifying
installation and setup.

LED indicators provide at-a-glance
operating status. Eight output contacts
are available for remote status indication.
RS232 ASCII communications port allows
setpoint control and remote monitoring.

Hot swappable
electronics module
and bypass feature
allow your protected
equipment to remain
up and running, even
when the SmartSwitch
is being serviced.