Installation Instructions and Owner’s Manual

Unvented LP-Gas Vent Free Room Heaters

WARNING: This appliance requires a 3/8” NPT

(National Pipe Thread) inlet connection to the

pressure regulator. Use of floor mounting feet will

require you to use a 3/8 NPT street elbow to make

gas connection.

CAUTION: Never connect heater directly to the Propane

supply. This heater requires an external regulator (not

supplied). Install the external regulator between the

heater and Propane/LP supply.

The installer must supply an external regulator. The ex-

ternal regulator will reduce the incoming gas pressure

to between 11 and 14 inches of water. If you do not

reduce incoming gas pressure heater regulator dam-

age could occur. Install external regulator with the vent

pointing down. Pointing the vent down protects it from

freezing rain or sleet.

CAUTION: Use only new black iron or steel pipe.

Internally-tinned copper tubing may be used in cer-

tain areas. Check your local codes. Use pipe of larger

enough diameter to allow proper gas volume to heater.

If pipe is too small, undue loss of pressure will occur.

Installation must include an equipment shutoff valve,

union and plugged 1/8” NPT tap. Locate NPT tap within

reach of test gauge hookup. NPT tap must be upstream

from heater (see figure 12).

Figure 12

*A CSA/AGA certified equipment shutoff valve with

1/8” NPT tap is an acceptable alternative to test gauge

connection. Purchase the CSA/AGA certified equipment

shutoff valve from your dealer.
IMPORTANT: Install an equipment shutoff valve in an

accessible location. The equipment shutoff valve is for

turning on or shutting off the gas to the appliance.
Apply pipe joint sealant lightly to male threads. This will

prevent excess sealant from going into pipe. Excess

sealant in pipe could result in clogged heater fuel train.

Pressure

Regulator

Heater

Cabinet

Ground Joint Union

Equipment

Shutoff Valve

From regulated LP tank

(11” W.C. to 14” W.C.

Pressure)

Tee Joint

1/8” NPT Plug Tap

Cap

Pipe Nipple

Tee Joint

3/8” NPT Pipe Nipple

Sediment

Trap

Test Gauge

Connection

Reducer Bushing

to 1/8” NPT

3” Minimum

CAUTION: Use pipe joint sealant that is resistant to

LP-Gas.

Install sediment trap in supply line as shown in figure

12. Locate sediment trap where it is within reach for

cleaning. A sediment trap traps moisture and con-

taminants. This keeps them from going into heater. If

sediment trap is not installed or is installed improperly,

heater may not run correctly.
IMPORTANT: Hold pressure regulator with wrench

when connecting it to gas piping and/or fittings.

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections for

leaks after installing or servicing. Correct all leaks

at once.
WARNING: Never use an open flame to check for

a gas leak. Apply a mixture of liquid soap and water

to all joints. Bubbles forming show a leak. Correct

all leaks at once.

PRESSURE TESTING GAS SUPPLY PIPING

SYSTEM
Test pressure in Excess of ½ psig (3.5kPa)

1. Disconnect appliance with its appliance main

gas valve (control valve) and equipment shutoff

valve from gas supply piping system. Pressures

in excess of ½ psig will damage heater regula-

tor.

2. Cap off open end of gas pipe where equipment

shutoff valve was connected.

3. Pressurize supply piping system by either using

compressed air or opening main gas valve on

or near gas meter.

4. Check all connections and joints in gas supply

piping system. Apply mixture of liquid soap and

water to gas joints. Bubbles forming show a

leak.

5. Correct all leaks at once.
6. Depressurize and relieve pressure in supply

piping system.

7. Reconnect heater and equipment shutoff valve

to gas supply.

8. Reconnected fittings must be checked for leaks

in next section.

Test Pressure Equal To or Less Than ½ psig (3.5 kPa)

1. Close equipment shutoff valve (see figure 13).
2. Pressurize supply piping system by either using

compressed air or opening main gas valve on

or near gas meter.

3. Check all joints from the gas meter to equip-

ment shutoff valve (see figure 14). Apply

mixture of liquid soap and water to gas joints.

Bubbles forming show a leak.