Understanding UPS Operation

3-2

EATON Powerware

®

9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

Bypass

Input

Rectifier

Input

Output

Path of electrical power

Battery

Rectifier

Inverter

Bypass

K4

Transformer

K3

(Closed)

CB1

Figure 3-1. Path of Current Through the UPS in Normal Mode

If the utility AC power is interrupted or is out of specification, the UPS automatically

switches to Battery mode to support the critical load with no interruption. When utility

power returns, the UPS returns to Normal mode.

If the UPS system becomes overloaded, the UPS switches to Bypass mode. The UPS

automatically returns to Normal mode when the error condition is cleared and system

operation is restored within specified limits.

If the UPS suffers an internal failure, it switches automatically to Bypass mode and remains

in that mode until the failure is corrected and the UPS is back in service.