Getting Started

2-6

EATON Powerware

®

9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

2.5.3 Power Distribution Module (LV models only)

An optional output Power Distribution Module (PDM) is available to distribute the output

power of the UPS to the critical load. The PDM cabinet has one or two panels, each

containing up to 42 poles for breaker switches. This arrangement provides flexibility for the

needs of your facility. Each panel is controlled by one 225A feeder breaker. The PDM is

enclosed in a separate cabinet that matches the UPS. This option requires a 480 to 208V

transformer.

2.5.4 Upgrade Capability

The UPS is available in various output power ratings in both 50 and 60 Hz models. If your

power requirements increase, you can upgrade the UPS system to provide more output

power with minimum impact on your facility.

2.5.5 Remote Monitor Panel

An optional Remote Monitor Panel (RMP) contains backlit status indicators and a local

horn, allowing you to monitor the operational status and alarm condition of the UPS from

virtually any location within your facility. You can install multiple RMPs at remote locations

to increase your monitoring capabilities. This option is described further in Chapter 6,

“Using Features and Options.”

2.5.6 Relay Interface Module

An optional Relay Interface Module (RIM) uses relay contact closures to indicate the

operating status and alarm condition of the UPS system. The module uses a serial interface

line and may support up to eight critical loads. This option is described further in

Chapter 6, “Using Features and Options.”

2.5.7 Input Isolation Transformer

Optional 480/480, 208/480, or 600/480 Vac input isolation transformers provide an isolated

input to the rectifier for applications that require a DC link that is not ground referenced

or for applications requiring an input of 208 or 600 Vac. The transformers are contained in

separate cabinets.

2.5.8 5% Input Filter

An optional 480/480 Vac 5% input filter reduces input harmonic current distortion and

minimizes upstream interference that can damage sensitive hardware components. The

filter is contained in a separate cabinet.