ME-300F and ME-400F Instruction Sheet

© 2011 Magnum Energy, Inc.

Conductor Gauge

Current Capacity*

Recommended Fuse

#4/0 AWG/107.16 mm²

360

400**

#2/0 AWG/67.4 mm²

265

300**

* - Current capacity based on 75° C cable rating in free air @ 30° C (86° F).

** - The next larger standard size overcurrent device may be used if the
de-rated cable ampacity falls between the standard overcurrent devices
found in the NEC.

FUSE

CLASS

-T

300

AMP

7.00" (17.78 cm)

6.25" (15.87 cm)

1.32"

(3.35 cm)

2.00"

(5.08 cm)

#10 (x4)

3/8 – 16 bolt w/ Hex nut (x4)

Requires 9/16" wrench

Figure 1, Large Fuse Block Dimensions

WARNING: During installation, incorrect stacking of the
fuse block hardware can create a highly resistive connec-
tion that generates heat. DO NOT place anything (i.e.,
washers) between the fuse and either battery cable
lug
as this can cause the fuse to overheat and blow open,
resulting in a partial melting of the fuse holder and cover.
Before stacking, refer to Figure 2.

Figure 2, Large Fuse Block Hardware Stacking

Mounting

Blocks

Battery

Cable Lugs

Hex Nuts

Fuse

Lock Washers

Table 1, Fuse Selection