ME-125F and ME-200F Instruction Sheet
© 2011 Magnum Energy, Inc.
Conductor Gauge
Current Capacity*
Recommended Fuse
#1 AWG/42.39 mm²
190
200**
#4 AWG/21.14 mm²
125
125
* - Current capacity based on 75° C cable rating in free air @ 30° C (86° F).
** - The next larger standard size overcurrent device may be used if the
de-rated cable ampacity falls between the standard overcurrent devices
found in the NEC.
~
5.00" (12.7 cm)
~
4.50" (11.43 cm)
1.25"
(3.17 cm)
.75"
(1.9 cm)
5/16 – 18 bolt w/ Hex nut (x2)
Requires 9/16" wrench
Figure 1, Small Fuse Block Dimensions
WARNING: During installation, incorrect stacking of the fuse
block hardware can create a highly resistive connection that
generates heat. DO NOT place anything (i.e., washers)
between the fuse and either battery cable lug as this can
cause the fuse to overheat and blow open, resulting in a partial
melting of the fuse holder and cover. Before stacking, refer to
Figure 2.
Figure 2, Small Fuse Block Hardware Stacking
Fuse
Battery Cable
Lugs
Flat Washers
Lock Washers
Hex Nuts
Table 1, Fuse Selection