Led diagnostics, Installation 1-12 – Yaskawa V7 PROFIBUS-DP User Manual
Page 18

Installation 1-12
 LED Diagnostics
The following table presents the faults displayed by the LEDs on the communication option, their causes, and solutions.
Table 1.8 – LED Diagnostics
LED Display
PWR
COM
ERR
WD
Content
Cause
Solutions
Power is not being supplied 
from the drive. 
• Check the main circuit wiring on the drive.
• Cycle drive power.
OFF OFF
OFF OFF
Power 
OFF 
Power is not being supplied to 
the option unit due to poor 
option unit connection. 
• Turn of the drive power.
• Check the option unit connection to the
drive.
• Cycle drive power.
Solid 
Green 
OFF
Solid 
Red 
Solid 
Red 
CPU 
Error 
Option unit CPU error.
• Cycle drive power. 
• Replace option unit if fault persists. 
Solid 
Green 
OFF
Solid 
Red 
Flashing 
Red 
Drive 
Error 
Error in Drive unit.
• Cycle drive power. 
• Replace V7 PROFIBUS-DP Option if fault 
persists
• Replace drive if fault persists.
Solid 
Green 
OFF
Flashing 
Red 
Solid 
Green 
Com 
Error 
A fault has occurred rendering 
communication impossible. 
• Check whether the address set in the
PROFIBUS-DP Master differs from the 
address of the option unit. 
• Check that the master is functioning
properly.
• Check that the termination resistor is
correctly connected to the communication 
line. 
• Check whether the communication line is
correctly connected (disconnected or poor 
connection). 
• Check that the communication line is
separated from the main power line.
Solid 
Green 
Solid 
Green 
Flashing 
Red 
Solid 
Green 
Com 
Error 
A fault has occurred rendering 
communication impossible. 
• Check whether the address is duplicated
with any other devices within the 
PROFIBUS-DP network. 
Solid 
Green 
Solid 
Green 
OFF
Solid 
Green 
CPU 
Init 
Option unit under initialization
• Wait until WD LED is flashing
Solid 
Green 
Solid 
Green 
OFF
Flashing 
Green 
Normal
Normal communication 
possible. 