Yaskawa SmartTrac PG Card User Manual
Page 10

SMART TRAC PG Card
6
••
Installing the Smart Trac PG Card Technical Manual TM 3554-0020
2CN
Connector
4CN
Connector
CPU Card
PG Card
PS Card
Ethernet
Card
Adapter
Ring
Card
Genius PCIM
Smart Trac
Card
PC/104
Optional
Smart Trac
Smart Trac
Smart Trac
Smart Trac
Card
Inverter Control
Main Chassis
Standoffs (4
places on top of
each card)
Figure 1.
Smart Trac PG Card Stack Position
1. Power off the Smart Trac AC1. Disconnect it and tag it as "Out of
Service". Perform this and all other steps required to remove all cards
located in a stack position above the PG Card. See "Appendix D –
Removing the Smart Trac Card Stack"
2. To replace the PG card, orient the PG card so that the PC/104
connector and the J2 connector align with the PC/104 connector on the
Smart Trac CPU card and the 4CN connector on the Inverter Control
board. Be careful to align the PC/104 connector pins with the
receptacle on the Smart Trac CPU card so the pins don’t bend when the
card is pushed into place.
3. Gently but firmly push the Smart Trac PG card onto the Smart Trac
CPU card. Make sure connecting pins are in alignment and J2 mates
with 4CN before pushing the two boards tightly together. Secure the
card using four (4) metal standoffs and one (1) plastic standoff.