YASKAWA ELECTRIC TOBP C730600 49A V1000 Option MECHATROLINK-II Installation Manual

6 MECHATROLINK Option Drive Parameters

6

MECHATROLINK Option Drive Parameters

Confirm proper setting of the all parameters in

Table 5

before starting network

communications.

Table 5 Parameter Settings

No.

Name

Description

Default

b1-01

<1>

Frequency Reference Selection

Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS communications
3: Option PCB
4: Pulse Input (Terminal RP)

1

b1-02

<1>

Run Command Selection

Selects the run command input source.
0: Operator - RUN and STOP keys on the digital
operator
1: Digital input terminals
2: MEMOBUS communications
3: Option PCB

1

F6-01

<2>

Communications Error Operation
Selection

0: Ramp to stop. Decelerate to stop using the
deceleration time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the
deceleration time in C1-09.
3: Alarm only.

1

F6-02

Selection of External Fault from
Communication Option Board

0: Always detected
1: Detection during run only

0

F6-03

<2>

Communication Option Fault
Stopping Method

0: Ramp to stop. Decelerate to stop using the
deceleration time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the
deceleration time in C1-09.
3: Alarm only.

1

F6-07

NetRef/ComRef Function Selection

0: Multi-step reference disabled (same as F7)
1: Multi-step reference enabled (same as V7)

1

F6-08

Reset Communication Parameters

0: Communication-related parameters (F6-††) are
not reset when the drive is initialized using A1-02.
1: Reset all communication-related parameters (F6-
††) when the drive is initialized using A1-02.

0

F6-20

<3> <4>

MECHATROLINK Station
Address

20 to 3FH

21

F6-21

<3>

MECHATROLINK Frame Size

0: 32 byte
1: 17 byte

0

F6-22

<3>

MECHATROLINK Link Speed

0: 10 Mbps
1: 4 Mbps

0