6 Supplemental Information - Flange Type Enclosure
12
YASKAWA TOEP YEASUP 03B Yaskawa AC Drive - A1000 & P1000 Manual Supplement
Installation Environment -
A1000 & P1000
Flange Type Enclosure
(NEMA 12 Backside)
Table 9 A1000 & P1000 Flange Type Enclosure Installation Environment
Removing the Shipping Package Attachments
Remove the shipping package attachments before installation.
Note: The number of screws varies in accordance with the drive model.
Figure 3
Figure 3 Removing the Shipping Package Attachments (example: Model 4A0675U)
Environment
Conditions
Installation Area
Indoors
Ambient Temperature
-10
°C to +40°C (Flange Type Enclosure)
Drive reliability improves in environments without wide temperature fluctuations.
When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air
temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
Humidity
95% RH or less and free of condensation
Storage Temperature
-20
°C to +60°C
Surrounding Area
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.
Altitude
Up to 1000 m without derating, up to 3000 m with output current and voltage derating.
Vibration
10 Hz to 20 Hz at 9.8 m/s
2
20 Hz to 55 Hz at 5.9 m/s
2
(Models 4T0058 to 0165) or 2.0 m/s
2
(Models 4T0208 to 0675)
Orientation
Install the drive vertically to maintain maximum cooling effects.
Screws
Shipping Package
Attachmet
Shipping Package
Attachmet
Top Side
Screws
Bottom Side