YASKAWA ELECTRIC TOEP YEAOPT 03 - V1000 Option DI-100 120 Vac Interface Installation Manual
2 Product Overview
2
Product Overview
◆
About This Product
The DI-100 option has seven optically isolated input terminals which can be used to connect
external 120 Vac control circuitry to the V1000 drive. The DI-100 Option mounts directly to
the V1000 control board terminals (S1 ~ S7 and SC). This option makes it possible to
control the V1000 digital inputs with 120 Vac.
This manual explains the handling, installation and specifications of this product.
Note: With this option is installed, safety input terminals H1 and HC on the V1000 drive are designed
to the functionality but are not certified to EN61800-5-1, EN954-1/ISO13849 Category 3, IEC/
EN61508 SIL2, Insulation cooridination: Class 1.
◆
Applicable Models
This option can be used with the drive models in
Table 1 Applicable Models
Drive Models
Model Notes
CIMR-VUBA0001
~BA0003
CIMR-VU2A0001
~2A0006
1-phase 200 V
and 3-phase 200 V
(small frame)
<1> Because the bottom cover/conduit bracket is discarded for DI-100 installation, the enclosure rating of these
models becomes IP00 or NEMA Open Type after DI-100 option installation.
CIMR-VUBA0006
thru BA0018
CIMR-VU2A0010
thru 2A0020
CIMR-VU4A0001
thru 4A0011
1- phase 200 V
3-phase 200/400 V
(medium frame)
CIMR-VU2A0030
thru CIMR-VU2A0069
CIMR-VU4A0018
thru CIMR-VU4A0038
3-phase 200/400 V
(large frame)