VS-616G5 Option Instruction Manual: InterBus-S Control Card SI-R
Related-Parameters
Notes:
*
EF0:
External Fault Signal from Serial Communication Option Card (SI-R).
Operation Signal Bit 8.
** BUS:
Serial Communication Error between Serial Communication Option Card (SI-R) and PLC.
***F9-05:
Torque Reference/Limit Selection:
Due to Torque Reference/Limit, cannot be set via SI-R option parameter F9-05. MUST
be set to “0” (Torque Reference/Limit from option disabled) when control method is set to
“Flux Vector Control” (A1-02 = 3).
Parameter
Number
Name
Description
Factory
Setting
b1-01
Frequency Reference Selection
0: Digital Operator
1: Terminal
2: Serial Communication
3: Option (Frequency Reference comes from SI-R option
card.
1
b1-02
Operation Method Selection
0: Digital Operator
1: Terminal
2: Serial Communication
3: Option (Run Command comes from SI-R option card)
1
F9-01
EF0* Contact Mode Selection
0: Fault at “1”
1: Fault at “0”
0
F9-02
EF0 Detection Mode Selection
0: Always detected
1: Only detected while in operation
0
F9-03
EF0 Stop Method Selection
0: Ramp to stop according to C1-02 setting
1: Coast to stop
2: Ramp to stop according to C1-09 setting (fast-stop)
3: Operation continues, alarm only
1
F9-04
Trace Sample Time
This parameter has no effect on SI-R card
0
F9-05
***
Torque Reference/Limit Selection
Flux Vector Control Mode Only:
0: Torque Reference/Limit from option disabled
1: Torque Reference/Limit from option enabled
1
F9-06
BUS** Stop Method Selection
0: Ramp to stop according to C1-02 setting
1: Coast to stop
2: Ramp to stop according to C1-09 setting (fast-stop)
3: Operation continues, alarm only
1