Yaskawa MP2000iec Series User Manual
Page 4

MP2000iec Series QRG Rev 3.3
1.5 Login to Webserver
KEY INFORMATION
Step
Description
Detail
1
Establish ethernet
communication with controller
See procedure 1.4 - type controller IP address into Internet Explorer to open the
controller's built in webserver.
2
Enter Login Credentials
Login:
Admin
(case sensitive).
Password:
MP2300S
(all caps, for MP2300Siec and MP2310iec).
Password:
MP2600
(all caps, for MP2600iec).
Password:
MP3200
(all caps, for MP3200iec)
Troubleshoot
The login configuration may have been customized. Obtain the login information
from the network administrator. Otherwise, the controller may be reset to factory
default using Motionworks IEC. See procedure __
1.6 Set IP Address of Controller
KEY INFORMATION
Step
Description
Detail
1
Login to Webserver
See Procedure. Login: Admin. Password: MP2300S, MP2600, MP3200, MP3300
2
Open "Ethernet Config"
On the left side
3
Set IP address
Select "Ethernet Config". Enter IP address and Subnet Mask. Click "Update Built-in
Ethernet Settings" to save.
4
Set default gateway
Select "Ethernet Config". Enter Default Gateway. If not gateway device exists on
the network, enter the same address as the IP address. Click "Update Built-in
Ethernet Settings" to save.
5
Turn off E-INIT switch
E-INIT must be off for configured ethernet settings to take effect at next reboot. If E-
INIT is left on, the address will be 192.168.1.1 regardless of the Ethernet Config
settings.
6
Reboot Controller
Under "Maintenance" -> reboot, then "Reboot Controller" and "OK" to confirm. Wait
45 seconds for reboot. The settings do not take effect until the controller is
rebooted with E-INIT off.
1.7 Update firmware
KEY INFORMATION
Do NOT update firmware in the field unless directed by Yaskawa.
DO update firmware before code development begins on new application.
Step
Description
Detail
1
Establish ethernet
communication with controller
See procedure 1.4 - type controller IP address into Internet Explorer to open the
controller's built in webserver.
2
Determine current firmware
version
The webserver welcome page lists the firmware version number, build number, and
build date
3
Acquire a firmware zip file
yaskawa.com/iecfw to download firmware files. Must log in to yaskawa.com
4
Login to Webserver
See Procedure. Login: Admin. Password: MP2300S, MP2600, MP3200, MP3300
5
Stop all motion
Operate the machine according to existing program.
6
Enable supervisor mode
Under "Maintenance" -> "Update Firmware", then click "enabled via software" and
"reboot controller". Wait 45 seconds for reboot.
7
Load firmware zip file
Under "Maintenance" -> "Update Firmware", then browse for firmware file, and
"upload". Upload takes about 1 minute. Do not attempt to unzip the firmware file.
8
Update firmware
Confirm the update version. Then click "update" button. The update takes about 2
minutes. Do not use the controller during this time.
9
Reboot Controller
Under "Maintenance" -> reboot, then "Reboot Controller" and "OK" to confirm. Wait
45 seconds for reboot.
Page 4 of 15