Yaskawa GPD515-XXXX-CS004 User Manual
Page 2

Added Parameters:
This software does not add any new parameters to the drive.
Changed Parameters:
Refer to Appendix 1 ot the GPD 515 Technical Manual, TM 4515. The following changes result from
the installation of this software in the drive.
Parameter
Function Name
Changed
Standard
1000 Hz
Software
Software
A1-02
Control Method Selection
Max. Value
3
0
Factory Setting
2
0
b3-03
Speed Search Deceleration
Min. Value
0.0
1.0
Time
b6-01
Dwell Frequency at Start
Max. Value
400.0
1000.0
b6-03
Dwell Frequency at Stop
Max. Value
400.0
1000.0
b8-02
Energy Saving Frequency
Max. Value
400.0
1000.0
C6-01
Carrier Frequency Upper Limit
Max. Value
15.0
(1)
10.0
(1)
C6-02
Carrier Frequency Lower Limit
Max. Value
15.0
(1)
10.0
(1)
d1-01 thru
Frequency References
Max. Value
400.0
1000.0
d1-08
Increment
0.01
0.1
d1-09
Jog Frequency Reference
Max. Value
400.0
1000.0
Increment
0.01
0.1
Factory Setting
6.00
60.0
d2-02
Reference Lower Limit
Max. Value
100.0
109.0
d3-01 thru
Critical Frequency Rejection
Max. Value
400.0
1000.0
d3-03
E1-04
Max Frequency
Max. Value
400.0
1000.0
E1-06
Base Frequency
Max. Value
400.0
1000.0
E1-07
Mid Frequency A
Max. Value
400.0
1000.0
E1-09
Min Frequency
Max. Value
400.0
1000.0
E1-11
Mid Frequency B
Max. Value
400.0
1000.0
H1-01 thru
Multi-Function Input Terminal
Max. Value
77
66
H1-06
Selection
L2-04
Power Loss V/F Ramp Time
Max. Value
2.0
5.0
L4-01
Speed Coincidence Level
Max. Value
400.0
1000.0
L4-03
Speed Coincidence Level + –
Max. Value
400.0
1000
Min. Value
–400.0
–1000
Increment
0.1
1
(1)
Setting will differ depending on drive capacity
Doc. No. 02Y00025-0420
Page 2 of 4
This Page: | Change | 0 | 4/18/97 |