2 main circuit wiring – Yaskawa Σ-II Series User Manual

Page 14

background image

E-12

* 1. Nominal value at the rated load. The specified derating is required to select an appropriate

fuse capacity.

* 2. Cutoff characteristics (25

°

C): 300% five seconds min. and inrush current of 20ms.

* 3. A preventive circuit for inrush current is not built in the 24 VDC control power supply.

The protective circuit must be designed by the customer.

* 4. Make sure the current capacity is accurate. For the SERVOPACK with the cooling fan built-

in, an inrush current flows; 200% of the current capacity in the table above for two seconds,
when turning ON the control circuit power supply to start the fan working.

Note: 1. Do not use a fast-acting fuse. Because the SERVOPACK’s power supply is a capacitor

input type, a fast-acting fuse may blow when the power is turned ON.

2. The SGDH and SGDM SERVOPACKs does not include a protective grounding circuit.

Install a ground-fault protector to protect the system against overload and short-circuit or
protective grounding combined with the molded-case circuit breaker.

10.2 Main Circuit Wiring

SGDH and SGDM SERVOPACKs are suitable under the following conditions.

• With 100 V class: Less than 5000 Arms, 120 V maximum.
• With 200 V class: Less than 5000 Arms, 240 V maximum.
• With 400 V class: Less than 5000 Arms, 480 V maximum.

SERVOPACKs must be used with UL-listed fuses or circuit breakers, in accordance with the
National Electrical Code (NEC).

Use 75

°C heat-resistant copper wires or an equivalent.

Three-
phase
400 V

0.45

05DE

1.1

1.6

0.7

∗4

10A

(24VDC)

∗3

600 V

480 V

1.0

10DE

2.3

3.4

1.5

15DE

3.2

4.6

2.0

20DE

4.9

7.1

20A

3.0

30DE

6.7

9.7

5.0

50DE

10.3

14.9

78A

6.0

60DE

12.4

17.8

1.2

∗4

20A

7.5

75DE

15.4

22.3

11.0

1ADE

22.6

32.7

1.3

∗4

40A

15.0

1EDE

30.9

44.6

(cont’d)

Main
Circuit
Power
Supply

SERVOPACK Model

Power Supply

Capacity per

SERVOPACK

(kVA)

Current Capacity of the

Molded-case Circuit

Breaker and the Fuse

(A

rms

)

1

,

2

Inrush Current

Rated Voltage

Capacity

(kW)

SGDM-

SGDH-

Main

Circuit
Power

Supply

Control

Circuit
Power

Supply

Main

Circuit
Power

Supply

Control

Circuit
Power

Supply

Fuse

MCCB