YASKAWA ELECTRIC TOBP C730600 40E 1000-Series Option AO-A3 Installation Manual
6 Related Parameters
6
Related Parameters
The parameters outlined in the following sections are used to set up the unit for operation
with the option. Set parameters as needed. Parameter setting methods can be found in the
drive unit Instruction Manual.
◆
Parameter Table
Table 5 Related Parameters
No.
(Addr.
Hex)
<1> The unit outputs voltage while this parameter is being adjusted. Voltage levels can be adjusted to match the
specifications of an external meter.
Name
Description
Values
F4-01
(391)
Terminal V1 Monitor Selection
Sets the monitor signal for output from
terminal V1. Set this parameter to the last
three digits of the desired U- monitor.
Some U parameters are available only in
certain control modes.
For example, enter “103” for U1-03.
Default when installed
to drive: 102 (output
frequency)
Default when installed
to energy-saving unit:
000 (reserved)
Range: 000 to 999
F4-02
(392)
Terminal V1 Monitor Gain
Sets the gain for voltage output via terminal
V1, where 100% equals 10 V output.
Terminal output voltage is limited to 10 V.
Default: 100.0%
Min: -999.9
Max: 999.9
F4-03
(393)
Terminal V2 Monitor Selection
Sets the monitor signal for output from
terminal V2. Set this parameter to the last
three digits of the desired U- monitor.
Some U parameters are available only in
certain control modes.
For example, enter “103” for U1-03.
Default when installed
to drive: 103 (output
voltage)
Default when installed
to energy-saving unit:
000 (reserved)
Range: 000 to 999
F4-04
(394)
Terminal V2 Monitor Gain
Sets the gain for voltage output via terminal
V2, where 100% equals 10 V output.
Terminal output voltage is limited to 10 V.
Default: 50.0%
Min: -999.9
Max: 999.9
F4-05
(395)
Terminal V1 Monitor Bias
Sets the amount of bias added to the voltage
output via terminal V1.
Default: 0.0%
Min: -999.9
Max: 999.9
F4-06
(396)
Terminal V2 Monitor Bias
Sets the amount of bias added to the voltage
output via terminal V2.
Default: 0.0%
Min: -999.9
Max: 999.9
F4-07
(397)
Terminal V1 Signal Level
Sets the voltage level for the analog output.
0: 0 to +10 Vdc
1: -10 to +10 Vdc
Default: 0
Range: 0, 1
F4-08
(398)
Terminal V2 Signal Level
Default: 0
Range: 0, 1