Page 19: Fer to, On p, 5 installation procedure
5 Installation Procedure
YASKAWA ELECTRIC TOBP C730600 40E 1000-Series Option AO-A3 Installation Manual
19
Ferrule-Type Terminals
Yaskawa recommends using CRIMPFOX 6 by Phoenix Contact or equivalent
ferrule-type terminals with the specifications listed in
Table 5
for wiring to ensure
proper connections.
Note: Properly trim wire ends so loose wire ends do not extend from the crimp terminals.
Table 3 Ferrule-Type Terminal Sizes
Terminal Functions
Table 4 Option Terminal Functions
Ferrule-Type
Terminal
Wire Gauge
mm
2
Phoenix Contact
Model
L
mm (in)
d1
mm (in)
d2
mm (in)
0.25 (24 AWG)
AI 0.25 - 6YE
10.5 (13/32)
0.8 (1/32)
2 (5/64)
0.34 (22 AWG)
AI 0.34 - 6TQ
10.5 (13/32)
0.8 (1/32)
2 (5/64)
0.5 (20 AWG)
AI 0.5 - 6WH
14 (9/16)
1.1 (3/64)
2.5 (3/32)
Terminal
Function
Signal Level
Description
V1
<1> Set the functions and output levels for terminals V1 and V2 using unit parameters. See the unit Instruction Manual
for directions on setting parameters.
Analog voltage output 1
-10 to 10 V
• Analog voltage output for an external monitoring
device
Output resolution 11-bit plus sign (1/2048)
• Max. load current 3 mA
V2
Analog voltage output 2
AC
Common
0 V
Common for analog voltage output
FE
Ground
–
Used for grounding shielded lines
d1
d2
6 mm
L