Table 6

lists the various fault codes related to the option. Refer to the drive Technical

Manual for further details on fault codes.
Check the following items first when an error code occurs on the drive:

• Are the cables connected properly and securely?

• Is the option is properly installed to the drive?

• Did a momentary power loss occur?

Table 6 Fault Displays, Causes, and Possible Solutions

Digital Operator Display

Fault Name

oFA01

Option Fault (CN5-A)
Option is not properly connected

Cause

Possible Solution

Option at drive port CN5-A was changed during

run.

Turn the power off and check the connectors between the drive

and option.

Digital Operator Display

Fault Name

oFb01

Option Fault (CN5-B)
Option is not properly connected

Cause

Possible Solution

Option at drive port CN5-B was changed during

run.

Turn the power off and check the connectors between the drive

and option.

Digital Operator Display

Fault Name

oFb02

Option Fault (CN5-B)
Two of the same options are connected simultaneously.

Cause

Possible Solution

AI-A3 option connected to CN5-B port while

another option was connected to CN5-A port.

Only one of the options: AI-A3, DI-A3, or SI-†† can be

connected to the drive at the same time.

Digital Operator Display

Fault Name

oFC01

Option connection error at drive port CN5-C

Cause

Possible Solution

Option at drive port CN5-C was changed during

run.

Turn the power off and check the connectors between the drive

and option.