6 Related Parameters
YASKAWA ELECTRIC
TOBP C730600 38C 1000-Series Option AI-A3 Installation Manual
25
H3-13
(41B) Analog Input Filter Time Constant
Sets a primary delay filter time constant for
terminals A1, A2, and A3. Used for noise filtering.
Default: 0.03 s
Min: 0.00
Max: 2.00
No.
(Addr.
Hex)
Name
Description
Analog
Output Level Unit
U1-21
(77)
Terminal V1 Input Voltage Monitor Displays the input voltage to terminal V1
on the option.
10 V: 100%
0.1%
U1-22
(72A) Terminal V2 Input Voltage Monitor
Displays the input voltage to terminal V2
on the option.
10 V: 100%
0.1%
U1-23
(72B) Terminal V3 Input Voltage Monitor
Displays the input voltage to terminal V3
on the option.
10 V: 100%
0.1%
No.
(Addr.
Hex)
Name
Description
Values