Lieber t PowerSure

®

Panel T VSS Technical Specifications

Low Exposure

Medium Exposure

Connection Type

Parallel

Parallel

Operating Voltage Range

±15%

±15%

Surge Current Capacity

25kA, 50kA or 100kA

100kA or 160kA

Fault Current Rating (AIC)

14kAIC

65kAIC

Dimensions

4.72"x4.72"x2.36"

(160 kA units)

8"x6"x4"

(100 kA units)

6"x4"x3"

Operating Frequency Range

47–63 Hz

47–63 Hz

Capacity

Continuous

Continuous

EMI/RFI Attenuation

40 dB typical

40 dB typical

Response Time

<0.5 nanoseconds

<0.5 nanoseconds

Dry Contract rating

125 VAC, 8.0A, 1.0pf

125 VAC, 8.0A, 1.0pf

Operating Temperature

-40°C to +50°C

-40°C to +50°C

Operating Humidity

0% to 95%

0% to 95%

Status Indication

LED, Dry Contacts

LEDs, Dry Contacts

Certifications

UL 1449, CUL(CE-optional)

UL 1449, CUL

Warranty

5-Years

5-Years

UL 1449 (second edition) Classification

Low Exposure

Medium Exposure

120 Volt systems

400 Volts all modes

400 Volts all modes

208 through 277 Volt systems

800 Volts all modes

800 Volts all modes

480 Volt systems

1,500 Volts all modes

1,500 Volts all modes

Ordering Information

Building a Low and Medium Exposure Model Number:

Examples

L P L 1 2 3

(Low Exposure Unit)

L P M 1 2 3

(Medium Exposure Unit)

Surge Current Capacity

Model ID

(Low Exposure)

100 kA/Phase

100

(L-N: 50 kA + L-G: 50 kA; N-G: 50 kA)

50 kA/Phase

50

(L-N: 25 kA + L-G: 25 kA; N-G: 25 kA)

25 kA/Phase

25-2

(L-N: 25 kA; N-G: 25 kA)

(Medium Exposure)

160 kA/Phase

160

(L-N: 80 kA + L-G: 80 kA; N-G: 80 kA)

100 kA/Phase

100-2

(L-N: 100 kA; N-G: 100 kA)

System Configuration

Model ID

Single (2 Wire + Gnd)

N or L

Split (3 Wire + Gnd)

S

Wye (4 Wire + Gnd)

Y

Delta Hi-Leg (4 Wire + Gnd)

H

Delta (3 Wire + Gnd)

D

Nominal Voltage Requirements

Model ID

L-N

L-L

L-G

120

N/A

120

120

120

208

120

120

120

240

240

120

N/A

208

208

208

230

400

230

230

N/A

240

240

240

277

480

277

277

N/A

400

400

400

N/A

480

480

480

(use Model ID column when

determining 1, 2, 3 portion

of Model Number)

{

1

3

2

Emerson Network Power.com

Emerson Network Power.

The global leader in enabling

Business-Critical Continuity

.

AC Power

Connectivity

DC Power

Embedded Computing

Embedded Power

Monitoring

Outside Plant

Power Switching & Controls

Precision Cooling

Racks & Integrated Cabinets

Services

Surge Protection

Liebert Corporation

1050 Dearborn Drive

P.O. Box 29186

Columbus, Ohio 43229

800 877 9222 Phone (U.S. &

Canada Only)

614 888 0246 Phone (Outside U.S.)

614 841 6022 FAX

Via Leonardo Da Vinci 8

Zona Industriale Tognana

35028 Piove Di Sacco (PD)

Italy

39 049 9719 111 Phone

39 049 5841 257 FAX

Emerson Network Power Asia Pacific

7/F., Dah Sing Financial Centre

108 Gloucester Rd, Wanchai

Hong Kong

852 25722201 Phone

852 28029250 FAX

liebert.com

Technical Support

800 288 6169 Toll-Free

607 724 2484 Phone

607 722 8713 Fax

While every precaution has been taken to ensure accuracy and

completeness in this literature, Liebert Corporation assumes no

responsibility, and disclaims all liability for damages resulting

from use of this information or for any errors or omissions.

© 2008 Liebert Corporation. All rights reserved throughout

the world. Specifications subject to change without notice.

All names referred to are trademarks or registered trademarks

of their respective owners.

® Liebert is a registered trademark of the Liebert Corporation.

SL-22034 (R06/08) Printed in USA

Business-Critical Continuity

, Emerson Network

Power and the Emerson Network Power logo are

trademarks and service marks of Emerson

Electric Co. ©2008 Emerson Electric Co.

800 288 6169 Toll-Free

607 721 8865 Phone

607 722 8713 Fax