5
www.powerware.com 1.800.356.5794
Technical specifications
General
User interface
Graphical LCD with blue backlight and text in English,
French, German, Portuguese, Italian and Spanish
LEDs
Four status-indicating LEDs
Topology
Double-conversion
Diagnostics
Full system self-test
UPS bypass
Automatic bypass
Dimensions
See model selection guide
Rail kit
Included with all units
Electrical input
Nominal voltage 208V, 230V
200V, 208V, 220V, 230V, 240V and 250V
user-selectable
Voltage range
156–280 Vac (output PF 0.7)
Power draw of
5000 VA: 24.0A @208V
UPS (full load)
6000 VA: 28.8A @208V
Recommended
35A
input breaker
rating
Frequency
50/60 Hz autoselect
Frequency range 40–70 Hz
Electrical output
Power factor
0.7
On utility voltage ±2% of nominal
regulation
On battery
±2% of nominal
voltage regulation
Efficiency
>97% in high-efficiency mode; 91% in normal mode
Frequency
±3% Hz online
regulation
Load crest
3 to 1
factor
Battery
Internal battery
5.5 Ah, sealed, lead-acid; maintenance free
type
External battery
Up to four per 9135, rail kits included for
modules
rack mounting
EBM battery type 5.5 Ah, sealed, lead-acid; maintenance free
Battery runtime
Four (4) minutes with internal batteries @100%
load
(0.7
PF)
For additional details, see battery runtime chart
Battery recharge Six (6) hours to recover 90 percent of nominal backup
time
time after 100 percent RCD load discharge
Battery
Hot-swappable internal and external batteries
replacement
Start-on-battery
Allows start of UPS without utility input
Communications
Serial port
RS-232 as standard, RS-232 cable provided
USB port
As standard (HID)
Relay output
DB-9 Dry Contact—common alarm as standard
Communications Optional communication slots (Mini X-Slot)
slot
Software
LanSafe UPS monitoring and management software
Environmental
Safety markings 208V: UL, NOM, NYCE
230V: CE, C-Tick, UL, GS
EMC markings
208/230V: FCC-A, VCCI-A, BSMI-A, C-Tick,
CE
Compliance
Audible noise
Max 46 dB
Ambient
0˚C (32˚F) to +40˚C (104˚F)
operating
Storage
-20˚C (-4˚F) to +40˚C (104˚F) with batteries and
temperature
-25˚C (-13˚F) to +55˚C
(131˚F)
without
batteries
Relative humidity 5–90% non-condensing
Heat dissipation (BTUs/hour)
Operating mode
Efficiency
5 kVA
6 kVA
Normal
91%
1150
1350
Battery
86%
1650
1960
High efficiency
97%
370
450
Back panel configurations
Choose from a variety of output receptacle combinations.
Back panel configurations vary by model type.
Hardwired models—230V
Hardwired models—208V
Power-corded models—208V