Type tests and environmental conditions – Westermo RFI-2xx User Manual
Page 9
9
6641-22310
Type tests and environmental conditions
Phenomena
Test
Description
Test levels
ESD
EN 61000-4-2
Enclosure contact
± 6 kV
Enclosure air
± 8 kV
RF field AM modulated IEC 61000-4-3
Enclosure
20 V/m 80% AM (1 kHz), 80 – 2700 MHz
Fast transient
EN 61000-4-4
Signal ports
± 2 kV
Power ports
± 2 kV
Surge
EN 61000-4-5
Signal ports
± 2 kV line to earth, ± 1 kV line to line
Power ports
± 2 kV line to earth, ± 1 kV line to line
RF conducted
EN 61000-4-6
Signal ports
10 V 80% AM (1 kHz), 0.15 – 80 MHz
Power ports
10 V 80% AM (1 kHz), 0.15 – 80 MHz
Power frequency
magnetic field
EN 61000-4-8
Enclosure
300 A/m 0, 16.7, 50, 60 Hz
Pulse magnetic field
EN 61000-4-9
Enclosure
300 A/m
Radiated emission
CISPR 16-2-3
Enclosure
Class B
ANSI C63.4
(FCC part 15)
Enclosure
Class B, 30 – 6500 MHz
Conducted emission
CISPR 16-2-1
DC power ports
Telecommunication
ports
Class B
Dielectric strength
EN 60950
Signal port to other
isolated ports
1.5 kVrms 50 Hz 1 min
Power port to other
isolated ports
1.5 kVrms 50 Hz 1 min
Temperature
EN 60068-2-1
EN 60068-2-2
Operating
–40 to +70ºC (all models)
Storage & Transport
–40 to +85ºC (all models)
Maximum surface
temperature
135 °C (temperature class T4)
Humidity
EN 60068-2-27
Operating
5 to 95% relative humidity
Storage & Transport
5 to 95% relative humidity
Altitude
Operating
2 000 m / 70 kPa
Service life
Operating
10 years
Vibration
IEC 60068-2-6
Operating
7.5 mm, 5 – 8 Hz
2 g, 8 – 500 Hz
(Wall-mounted or DIN-rail mounted using TH
35-15 according to EN 60175)
Shock
IEC 60068-2-27
Operating
15 g, 11 ms
(Wall-mounter or DIN-rail mounted using TH
35-15 according to EN 60175)
Enclosure
UL 94
Aluminium / Zink
Flammability class V-0 (all models)