Specifications – Westermo RD-48 User Manual
Page 17

17
6153-2004
Model description
RD-48 LV RD-48 LV TEMP
RD-48 HV
Rated voltage
12–48 VDC
95–240 VAC
110–250 VDC
Operating voltage
9.6–57.6 VDC
85.5–264 VAC
88–300 VDC
Rated current
300 mA
50 mA
Rated frequency
–
48–62 Hz
Polarity
Reverse polarity protected
Polarity independent
Connection
2-position screw terminal
3-position screw terminal
Connector size
0.2 – 2.5 mm² (AWG 24-12)
Fuse
To be externally fused.
4. Specifications
4.1 Connections
Power interface
RS-422/485 interface – Line A
Electrical specification
RS-422/485
Data rate
300 bit/s – 1.5 Mbit/s
Connection
4-position screw terminal
Connector size
0.2 – 2.5 mm² (AWG 24-12)
Circuit type
TNV-1
RS-422/485 interface – Line B
Electrical specification
RS-422/485
Data rate
300 bit/s – 1.5 Mbit/s
Connection
4-position screw terminal
Connector size
0.2 – 2.5mm² (AWG 24-12)
Circuit type
TNV-1
4.2 Insulation between interfaces
Power (RD-48 HV) to all other
3.0 kV RMS @ 50Hz and 60 s duration
Power (RD-48 LV) to all other
1.0 kV RMS @ 50Hz and 60 s duration
Line-A to Line-B
1.5 kV RMS @ 50Hz and 60 s duration
4.3 Climatic environment
Temperature, operating
5 to 55°C
–40 to 70°C (TEMP version)
Temperature, storage and transportation
–40 to 70°C
Relative humidity, operating
5 to 95% (non-condensing)
Relative humidity, storage and transportation 5 to 95% (condensation allowed
outside packaging)