Interface specifications – Westermo Viper 408 User Manual
Page 9

9
6641-2201
Interface specifications
Power and fault relay port PWR
Rated voltage
24 to 110 VDC
Operating voltage
24 to 110 VDC ±40%
Rated current
40 mA @ 110 VDC
140 mA @ 24 VDC
Rated frequency
DC
Inrush current, I
2
t
Max 0.02 A
2
s @ 24 – 110 VDC
Startup current *
7 A
peak
@ 24 – 110 VDC
Polarity
Reverse polarity protected
Redundant power input
No
Isolation to
Connections X1 – X8 and to ground, 1500 VAC.
Fault relay belongs to the same isolation group as the power
supply lines (fault relay signals are also contained within
PWR).
Connection
4 pin male M12 connector with A-code
Connector size
M12, recommended cable area 0.5 mm
2
recommended
(minimum 0.25 mm
2
), cable dimensions depend on choice of
M12 connector
Shielded cable
Not required, twisted pair is recommended
Fault relay resistance
< 10 Ω
Operating voltage
Up to 110 VDC
Max continuous current
250 mA
* If external power supply is used it must meet specified startup current.
M12 A-Coded
Power
Connector
Position
Direction
Description
1
U+
Positive supply voltage
2
Out
Alarm relay (status) +
3
0 V
Negative supply voltage
4
Out
Alarm relay (status) –
Housing
Shield
Chassis of product (ground)