6651-2211

PROFIBUS DP (RS-485)

Electrical specification

EIA RS-485 / EN 50 170

Data rate

9 600 bit/s, 19.2, 93.75, 187.5, 500 kbit/s, 1.5, 3, 6 and 12 Mbit/s

Data format

8 data bits, even parity, 1 stop bit, 11 bits total

Protocol

PROFIBUS DP / EN 50170

Data Rate detection

Yes, compliant with EN 50 170

Retiming

Yes

Turn around time

In accordance with EN 50 170

Transmission range

≤ 1200 m, depending on data rate and cable type (EIA RS-485)

Settings

None, external termination and failsafe biasing

Protection

Installation Fault Tolerant (up to ±60 V)

Isolation to

Power and Status port

Connection

9-pin D-sub female

Shielded cable

Not required

Conductive housing

Isolated to all other circuits and housings

LED Indicators(for details see page 15)