6651-2211
PROFIBUS DP (RS-485)
Electrical specification
EIA RS-485 / EN 50 170
Data rate
9 600 bit/s, 19.2, 93.75, 187.5, 500 kbit/s, 1.5, 3, 6 and 12 Mbit/s
Data format
8 data bits, even parity, 1 stop bit, 11 bits total
Protocol
PROFIBUS DP / EN 50170
Data Rate detection
Yes, compliant with EN 50 170
Retiming
Yes
Turn around time
In accordance with EN 50 170
Transmission range
≤ 1200 m, depending on data rate and cable type (EIA RS-485)
Settings
None, external termination and failsafe biasing
Protection
Installation Fault Tolerant (up to ±60 V)
Isolation to
Power and Status port
Connection
9-pin D-sub female
Shielded cable
Not required
Conductive housing
Isolated to all other circuits and housings
LED Indicators(for details see page 15)