beautypg.com

Interface specifications – Westermo ODW-710-F2 User Manual

Page 11

background image

11

6651-2211

Interface specifications

* External supply current capability for proper startup

Power

Rated voltage

ODW-710-F2:

12 to 48 VDC and 24 VAC

ODW-710-F2 Ex: 12 to 48 VDC

Operating voltage

ODW-710-F2:

10 to 60 VDC and 20 to 30 VAC

ODW-710-F2 Ex: 10 to 60 VDC

Rated current

400 mA @ 12 VDC
200 mA @ 24 VDC
100 mA @ 48 VDC

Rated frequency

ODW-710-F2:

DC and 48 to 62 Hz

ODW-710-F2 Ex: DC

Inrush current I

2

t

0.2 A

2

s

Startup current*

1.0 Apeak

Polarity

Reverse polarity protected

Redundant power input

Yes

Isolation to

PROFIBUS DP and Status port

Connection

Detachable screw terminal

Connector size

0.75 – 2.5 mm

2

(AWG 18 – 13)

Connect the unit using at least 18 AWG (0.75 mm

2

) wiring

Shielded cable

Not required

Status

Port type

Signal relay, changeover contacts

Rated voltage

Up to 48 VDC

Operating voltage

Up to 60 VDC

Contact rating

500 mA @ 48 VDC

Contact resistance

< 50 mW

Isolation to

PROFIBUS DP and Power port

Connection

Detachable screw terminal

Connector size

0.2 – 2.5 mm

2

(AWG 24 – 13)

Shielded cable

Not required

This manual is related to the following products: