Type tests and environmental conditions – Westermo DDW-226 User Manual
Page 10
10
6642-22402
Type tests and environmental conditions
Phenomena
Test
Description
Test levels
ESD
EN 61000-4-2
Enclosure contact
± 6 kV
Enclosure air
± 8 kV
RF field AM modulated IEC 61000-4-3
Enclosure
10 V/m 80% AM (1 kHz), 80 – 1000 MHz
20 V/m 80% AM (1 kHz), 800 – 1000 MHz
10 V/m 80% AM (1 kHz), 1400 – 2100 MHz
5 V/m 80% AM (1 kHz), 2100 – 2500 MHz
1 V/m 80% AM (1 kHz), 2500 – 2700 MHz
Fast transient
EN 61000-4-4
Signal ports
± 2 kV
Power ports
± 2 kV
Surge
EN 61000-4-5
Signal ports unbalanced
± 2 kV line to earth, ± 2 kV line to line
Signal ports balanced
± 2 kV line to earth, ± 1 kV line to line
Power ports
± 2 kV line to earth, ± 1 kV line to line
RF conducted
EN 61000-4-6
Signal ports
10 V 80% AM (1 kHz), 0.15 – 80 MHz
Power ports
10 V 80% AM (1 kHz), 0.15 – 80 MHz
Power frequency
magnetic field
EN 61000-4-8
Enclosure
300 A/m
Pulse magnetic field
EN 61000-4-9
Enclosure
300 A/m
Mains freq. 50 Hz
EN 61000-4-16
Signal ports
100 V 50 Hz line to earth
Mains freq. 50 Hz
SS 436 15 03
Signal ports
250 V 50 Hz line to line
Voltage dips
and interruption
EN 61000-4-29
DC power ports
10 & 100 ms, interruption
10 ms, 30% reduction
10 ms, 60% reduction
+20% above & –20% below rated voltage
Radiated emission
EN 55022
Enclosure
Class A
EN 55016-2-3
Enclosure
Class A
FCC part 15
Enclosure
Class A
Conducted emission
EN 55022
DC power ports
Class A
Dielectric strength
EN 60950
Signal port
to other isolated ports
1500 Vrms 50 Hz 1 min
Temperature
Power port
to other isolated ports
1500 Vrms 50 Hz 1 min
Operating
–40 to +70ºC*
Storage & Transport
–40 to +85ºC
Maximum surface
temperature
135°C (temperature class T4)
Humidity
Operating
5 to 95% relative humidity
Storage & Transport
5 to 95% relative humidity
Altitude
Operating
2 000 m / 70 kPa
Reliability prediction
(MTBF)
MIL-HDBK-217F
Operating
700 000 hours @ 25°C
Service life
Operating
10 year
Vibration
IEC 60068-2-6
Operating
7.5 mm, 5 – 8 Hz
2 g, 8 – 500 Hz
Shock
IEC 60068-2-27
Operating
15 g, 11 ms
Enclosure
UL 94
Aluminium/Zink
Flammability class V-0
Dimension W x H x D
134 x 105 x 122 mm
Weight
1.5 kg
Degree of protection
IEC 529
Enclosure
IP 40
Cooling
Convection
Mounting
Horizontal on 35 mm DIN-rail or wall-mouonted
* Refer to “Safety” section in User Guide.