Westermo ODW-720-F2 User Manual
Page 12

12
6651-2235
RX2
TX2
Device 1
Receiving data from
device 4 on the
primary channel
Device 2
Receiving data from
device 5 on the
secondary channel
Device 3
Not sending
or receiving any data
Device 5
Sending data to
device 2 on the
secondary channel
TX1
RX1
RX2
TX2
TX1
RX1
RX2
TX2
RS-232
RS-232
RS-232
Fibre
pair
Fibre
pair
Fibre
pair
RS-232
TX1
RX1
RX2
TX2
TX1
RX1
PWR
FP
TD
RD
PWR
FP
TD
RD
PWR
FP
TD
RD
PWR
FP
TD
RD
Device 4
Sending data to
device 1 on the
primary channel
RS-232
Fibre
pair
RX2
TX2
TX1
RX1
PWR
FP
TD
RD
The fifth ODW-720 unit recieives data from communications device 5 on the RS-232
port and sends it out on optical fibre TX2 using the secondary data channel.
The fourth ODW-720 unit receives secondary channel data on optical fibre RX1.
Secondary channel data is repeated out on optical fibre TX2. The fourth ODW-720 unit
also receives data from communications device 4 on the RS-232 port. The RS-232 data is
sent out on optical fibre TX2 using the primary data channel.
The third ODW-720 unit receives both primary and secondary channel data on optical
fibre RX1. Both primary and secondary data are repeated out on optical fibre TX2. None
of the data is sent out on the RS-232 port.
The second ODW-720 unit receives both primary and secondary channel data on optical
fibre RX1. Both primary and secondary data are repeated out on optical fibre TX2, but
only the secondary channel data is sent out on the RS-232 port.
The first ODW-720 unit receives both primary and secondary channel data on optical
fibre RX1, but only the primary channel data is sent out on the RS-232 port.